Permit Number: D05-0034
Parcel: 136075680

Address:
9484 E 22ND ST

Review Status: Completed

Review Details: REVISION - DEV PLAN

Permit Number - D05-0034
Review Name: REVISION - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/15/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond May 11, 2007

To: Peter Salonga, Otracle Engineering Group

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter(520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: World Savings
Development Plan – 5th Submittal
D05-0034

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Sheet 2: Two of the cleanouts are marked as CO #1, please revise.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
05/22/2007 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond 1) Prepare the trail easement referred to on the plans. Obtain City of Tucson acceptance prior to recording. No Certificate of Occupancy will be issued until the easment is accepted by the City of Tucson and recorded.

2) A minimum distance of two (2) feet must be maintained between a PAAL and any wall, screen, or other obstruction.

Revise the plans to locate the required screen along Harrison Road as required by DS 3-05.2.2.B.2. Refer to LUC 3.7.3.2.C for limitations on locating screening with the street landscape border.


RESUBMITTAL OF AL PLANS IS REQUIRED
05/31/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond Call out for 25' radius curb returns.
05/31/2007 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D05-0034
World Savings
Development Plan

TRANSMITTAL DATE: May 30, 2007

DUE DATE: June 8, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Please include the contour interval on each sheet of the development plan with the north arrow.
DS 2.05.2.1.H

2. The separate response letter detailing compliance to applicable rezoning conditions of C9-00-03 does not provide must detail as to how compliance to rezoning conditions was accomplished. For example for rezoning condition 9a the response would state a copy of the required report was provided to the president of the "X" Neighborhood for review on April 10th. Please provide a detailed response letter.
DS 2-05.2.4.U

3. Please label drive-through lane being serviced by the ATM as "ATM Service Only" on the development plan.

4. Please revise bicycle detail 1 showing proposed class 2 bicycle parking spaces. The required spacing between bicycle parking space must be a minimum of thirty (30) inches.

The type of rack proposed does not provide two-point support for bicycles. The rolling rack is an unacceptable design since it does not provide for two-point support. Bicycle can easily fall over and damage. Please review DS 2-09.8.0 Figure 2 - 7 for acceptable and unacceptable rack designs and Figure 9 for dimensional requirements.
DS 2-09.5.1, DS2-09.5.2, DS 2-09.5.4, & DS 2-09.6.2

5. The proposed monument sign proposed on 22nd Street appears to be placed within the future sight visibility triangle. Lines of sight cannot be obscured between thirty (30) inches and six (6) feet through a triangle area adjacent to a driveway, a PAAL, or a street, where such access ways intersect with another street in a T-configuration. Please revise location of proposed monument sign.
DS 3-01.5.1.A.1

6. The PAAL on the east side is dimensioned as twenty-three and one half (23 1/2) feet. The minimum width allowed for a two-way PAAL is twenty-four (24) feet. Please revise.
DS 3-05.2.1.C.1

7. Please dimension the PAAL on the west side of the building.

8. Please demonstrate that a delivery vehicle can maneuver around the southwest corner of the site without having to cross into the required stacking area. The radius is based on the national standards for turning radii required for vehicles for which the loading space is designed.
LUC 3.4.4.2.C

9. Please revise wording used in bicycle parking calculations. It should read 8% of "provided" vehicle parking, not required, and the calculation should be 0.08x"25", not 24.
LUC 3.3.3.5

10. The dumpster location is within fifty (50) feet of R-1 zoned property (common area "A", Harrison Terrace). Per rezoning condition 19 all dumpsters are to be placed at least fifty (50) feet from residentially zoned or developed property. Please revise location.
C9-00-03 Condition 19

11. All changes, modifications, and/or corrections must be made on all applicable plans including the development plan, landscape plan, and NPPO. Once changes, modifications, and/or corrections are made and reviewed further comments may result.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 74960.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D05-0034dpr1.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
06/11/2007 SUNRISE ENGINEERING ENGINEERING REVIEW Denied June 7, 2007


City of Tucson
201 N. Stone Ave.
Tucson, Arizona 85726


RE: Plan Review: World Savings- 9484 E 22nd St.
Applicant: Steven Miller


Sunrise Engineering’s Civil Engineering Plan Review Team has completed the 4th review of the following documents on behalf of the City of Tucson Development Services Department:

Plans: One (1) copy (5 sheets) with cover sheet dated April 5, 2006.


These documents were not reviewed since these are not the newer, revised plans.

Drainage Report: One (1) report, dated May 7, 2007.

All the drainage report comments were addressed.

At this time we do not recommend approval. If you have any questions regarding these comments, please contact the reviewer Stephanie Schramm at 520-723-8634, between 8:00 A.M. and 5:00 P.M., Monday through Friday.


Sincerely,
SUNRISE ENGINEERING, Civil Engineering Plan Review Team




Stephanie Schramm, P.E.
Project Manager
06/13/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D05-0034 World Savings 06/13/07

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-00-03

NEIGHBORHOOD PLAN: Pantano East Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: June 8, 2007

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments from 12/26/06.









REVIEWER: msp 791-4505 DATE: June 8, 2007
06/21/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: June 21, 2007

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: D05-0034: World Savings: Development Plan Review(5-10-07)

Approved.
07/11/2007 CDRC1 COT NON-DSD REAL ESTATE Approved Re: D05-0034 World Savings
07/12/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 12, 2007

Steve Miller
World Savings
1901 Harrison Street
Oakland, CA. 94612

Subject: D05-0034 World Savings Revised Development Plan

Dear Steve:

Your submittal of May 10, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Development Plan (Traffic, Landscape, Wastewater, Zoning, Engineering, DSD)

4 Copies Revised Landscape Plans (Zoning, Landscape, Engineering, DSD)









Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 510-446-4509 & 292-6144 (attn: Pete Salonga)
07/12/2007 PGEHLEN1 POLICE REVIEW Passed