Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: D05-0030
Parcel: 14029043A

Review Status: Completed

Review Details: REVISION - DEV PLAN

Permit Number - D05-0030
Review Name: REVISION - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/09/2006 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Subject to DSMR for basin slopes. ADD DSMR case number to the development plan.
06/12/2006 JIM EGAN COT NON-DSD FIRE Approved
06/22/2006 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering does not approve the development plan due to the incorrect sight visibility triangles (SVT)

Near SVT from a Driveway/PAAL to an Arterial, MS&R, shall be 345'

Far should be a pedestrian (as shown ok)

Measure these at both existing, and projected (future) face of curb.
06/23/2006 JCLARK3 ENV SVCS REVIEW Approved
07/11/2006 LOREN MAKUS ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator DATE: July 11th, 2006

SUBJECT: Engineering review of the Development Plan, Starbucks. The activity number is D05-0030.

SUMMARY: The Development Plan and Drainage Report were received by Engineering on June 9th, 2006. Engineering has reviewed the received items and does not recommend approval of the Development Plan.

RESUBMITTAL REQUIRED: DEVELOPMENT PLAN


DEVELOPMENT PLAN

1. The length of a Nearside SVT from a Driveway/PAAL to an Arterial Road shall be 345'. Revise the development plan to show the correct SVT. DS 3-01.5.1.

2. The Zoning Reviewer David Rivera requested from the previous review to show a 6' wide sidewalk at the future sidewalk location. Be advised the shown 6' sidewalk does not scale to 6'. It is acknowledged a 6' width is labeled on the plan. The 3' gap between the back of curb and front of sidewalk has been accommodated, however when scaled the sidewalk only scales to 4'. Revise the plan appropriately.

3. The loading space and the solid waste enclosure appear to not be accessible from the each vehicle for appropriate use. Show on the plan view the solid waste vehicle maneuverability to the solid waste enclosure, with the inside and outside radius fully dimensioned per the Development Standard 6-01. For the loading space, provide on the plan view the AASHTO minimum turning radius (inside and outside) for the vehicle design type accessing the loading space. If the vehicle maneuverability can not be shown on the plan without obstruction, this office recommends setting up a meeting with David Rivera, John Clark, Loren Makus and Patricia Gilbert to reach a solution for vehicle maneuverability for the loading space and the solid waste enclosure.
07/17/2006 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: D05-0030
Star Bucks at Valencia
Development Plan

TRANSMITTAL: July 17, 2006

DUE DATE: July 10, 2006

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

It has been suggested by the Engineering reviewer Patricia Gilbert that a meeting occur with you and anyone else you feel necessary in order to go over and resolve the remaining issues prior to re-submittal of the development plan. None of the zoning comments have been addressed fully and have been left in their entirety.


1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is August 23, 2006

2. The previous comment was partially addressed. Please remove the subject to section listed after the General Merchandise uses. The subject to section 3.5.4.7 is not applicable to the General Merchandise use in the I-1 Zone.

(Previous Comment left as reference for the zoning reviewer.) This comment was not completely addressed. Please revise or add the following. Revise general note two on sheet two as follows. In the land use code under the I-1 zone the Food Service use is subject to performance criteria section 3.4.5.6.C. List the subject to section next to the restaurant use. Also revise the words restaurant use to Food Service Use. The words retail use should be revised to the specific use such as General Merchandise, Food and Beverage Sales, etc and include if applicable the subject to section number. Revise as required.

Previous Comment: Please, clarify what the retail use is going to be i.e., general merchandise, food store, etc. Submit a dimensioned copy of the floor plan for the proposed building to verify square footage and design. General notes number two must be revised to include any applicable subject to section numbers for each use. DS 2-05.2.2.B.3

3. The Dumpster locations have been relocated to a location over an existing utility and access easement. Please get confirmation from the utility companies that the location of the enclosure is not and issue for them. Written approvals on the companies letter head ensuring that the companies have no objection to the placement of the enclosure over the utility easement should be provided.

The previous comment has been left for the reference by the reviewer to ensure that the recordation information is listed on the plan prior to zoning approval unless other accommodations are made with the Zoning Manager Patricia Gehlen.

Previous Comment: All existing and proposed easements must be drawn on the development plan. The existing easement location, purpose, width, and recordation information must be labeled. DS 2-05.2.3.C

All proposed easements must be recorded by separate instrument and shown on the development plan along with the recordation docket and page number prior to approval of the development plan. DS 2095.2.4.G

4. All sidewalks for arterial streets are to be constructed at a width of six feet. Please revise the drawing to depict a future sidewalk of six feet wide.

(Previous Comment left as reference for the zoning reviewer.) It does not appear that the future curb and sidewalk have been correctly depicted on the plan. Valencia Road is slated to be widened to a total 150 feet of right of way. The future curb is to be constructed 12 feet from the future right of way line. The plan is depicted with a sidewalk or curb location greater than depicted on the cross section in development standards 3-01. Please review the development standards and revise the plan as required. Also please consult with the Engineering reviewer for more information on this issue.

Previous Comment: Draw, dimension, and label the future curb and sidewalk for Valencia Road. Add a building setback from the future back of curb location to the building. (It is acknowledged that the building meets the required building setback from the existing back of curb.) DS 2-05.2.4.F

5. Per a meeting with the Engineering staff the maneuverability into and out of the loading zones on both the Starbucks and Popeye's parcels must be demonstrated and must comply with the minimum radius used for Refuse trucks, 35-foot inside and 50-foot outside.

(Previous Comment left as reference for the zoning reviewer.) The maneuverability has not been demonstrated on the plan. Please contact the Engineering reviewer for information on radius requirements for demonstration of maneuverability into and out of the loading zone.

Previous Comment: Demonstrate maneuverability into and out of the loading zone. In the real world most loading zones are not utilized because the maneuverability is never realistically depicted on the plan and therefore never works on the site. Please ensure that the loading is accessible and useable. DS 2-05.2.4.O

6. Per our staff meeting additional issues came up that were not apparent due to fact that the same reviewer was not reviewing the adjacent development plans. The following have been noted as items that must be addressed.

a. The location of the dumpsters on the Starbucks proposed due not appear to have adequate access to the enclosure area as required per the development standards. The maneuverability to service the Dumpster has not been demonstrated. Demonstrate compliance or approval of a development standard modification is required.
b. The Starbucks and Popeye's developments will essentially function as one site and should have been submitted as such even if the developments are on separate properties. This development should have cross access, parking, and pedestrian agreements.
c. The handicap access ramp next to the H.C. parking has not been drawn correctly. Please see ANSI standard Fig. 406.3 page 24.
d. An access ramp has not been provided at the both ends of the sidewalks, which are along the north end of the building. Also add a detail depicting the proposed access ramps for the sidewalk from the property line to the front of the building. Label the truncated domes for both of the access ramps.
e. A plan view of the bicycle parking detail has been provided. Include a vertical or elevation detail of the proposed rack and list the type, manufacturer and the number of bicycles the rack supports.
f. Dimension the west PAAL area along the north side of the development.
g. Per plat book 37 at page 50, a requirement for a 50-foot industrial easement and a 30-foot drainage easement is required. Discuss the drainage easement with the Engineering Reviewer.
h. Clarify if the access from the Starbucks development will be provided to the development along the West Side of the site. It appears that PAAL area can and may be opened to provide cross access. If this is the case, provide a copy of the recorded cross access agreement document.
i. Per Map and Plat 37/50 general note 9, "Signed sewer agreements for lots 1-46 are required prior to issuance of building permits by the Zoning Inspector." I'm sure that this agreement has been taken care but please provide the agreement document.

7. Additional comments may be forthcoming based on revisions to the plans and responses to the zoning comments.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

DGR C:\planning\cdrc\developmentplan\D050030dp4.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, and additional requested documents.
07/21/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 21, 2006

Antony C. Tsang
A.C. Tsang Engineering Group, Inc.
4626 East Fort Lowell, Suite S
Tucson, AZ 85712

Subject: D05-0030 Starbucks at Valencia Development Plan

Dear Tony:

Your submittal of June 9, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

4 Copies Revised Development Plan (Traffic, Zoning, Engineering, DSD)

3 Copies Revised Landscape Plans (Zoning, Engineering, DSD)

Review period extension granted until August 23, 2007 as long as development plan is revised to meet all code revisions adopted since August 24, 2005.




Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 325-0979