Permit Number: D05-0025
Parcel: 11446213B

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D05-0025
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/22/2005 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The screening required along Super Chicken Drive and Desert Links Drive is 30" per LUC 3.7.3.6.A. If the requirement were 5 feet the plan would not be acceptable due to planting elevation of some of the plants, nor would it match the site plan proposal for 30" walls along one segment. Revise the landscape plan screening descriptions on sheet 2.
2) Revise the landscape plan to specify the correct wall height for the loading zone screen. 6 feet is the minimum height. LUC Table 3.7.2-I.
3) Revise the development and landscape plans to locate the loading area screen walls such that the loading area is completely screened from Desert Links Drive.
4) The development plan lists C9-91-19 as a related case, add this same reference to the landscape plan. DS 2-07.2.0
5) Revise the landscape plan to eliminate any gaps in screening along Super Chicken Drive, while locating the screening elements behind or within the 3' allowance in the landscape border. LUC 3.7.3.2.C
09/28/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: DESERT LINKS RETAIL

D05-0025





Tucson Electric Power Company has reviewed and approved the development
plan submitted for review September 21, 2005.



Please call me at (520) 917-8745, should you have any questions.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
09/29/2005 JCLARK3 ENV SVCS REVIEW Approv-Cond * Enclosure requires rear and side wall protection.
Enclosure needs to be positioned to be perpendicular to the E-W PAAL.
10/07/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this DP.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
10/07/2005 PAUL MACHADO ENGINEERING REVIEW Approved
10/18/2005 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: D05-0025
Desert Links Retail
Development Plan

TRANSMITTAL: 10/18/05

DUE DATE: 10/04/05

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is July 4, 2006.

2. For consistency with the land use code sections, please revise the loading zone note to sate the correct loading zone matrix table section number from 3.4.5.5 to "3.4.5.3".

Previous Comment: Please correct the loading zone matrix table noted in the loading zone calculation from 3.4.5.5 to "LUC Table 3.4.5.3". DS 2-04.2.4.O


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

DGR C:\planning\cdrc\developmentplan\D050025dpca.doc
10/20/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond October 19, 2005

To: Kevin M Hall, DCC Company

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Desert Links Retail
Development Plan – 2nd Submittal
D05-0025

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



Sheet 1: Revise General Note #13 to show the proposed number of wastewater fixture unit equivalents being installed in the proposed building.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
10/21/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

October 21, 2005

Kevin M. Hall
DCC Company
2828 North Country Club, Suite 100
Tucson, AZ 85716

Subject: D05-0025 Desert Links Retail Plan

Dear Kevin:

Your submittal of September 21, 2005 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

3 Copies Revised Development Plan (Landscaping, Environmental Services, DSD)

2 Copies Revised Landscape Plans (Landscaping, DSD)




Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 829-7856