Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D05-0014
Parcel: 12907004A

Address:
1820 E 22ND ST

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D05-0014
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/29/2005 JIM EGAN COT NON-DSD FIRE Approved The Development Plan is approved April 29, 2005.
05/05/2005 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D05-0014 OASIS BOTTLED WATER/DEVELOPMENT PLAN
DATE: May 5, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:


Add recording book and page for Neff Addition in Title Block.

Delete 22nd Street Access Road (one way) on sheets 1 and 2.

Delete 1230 S. Campbell, LLC (south of this project) on sheets 1 and 2.

Correct Martin Street to Martin Avenue on sheets 1 and 3.













jg
05/05/2005 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
D05-0014
OASIS BOTTLED WATER
05/06/2005 JCLARK3 ENV SVCS REVIEW Denied * No known landfill with in 1000 feet of this development.
* Enclosure detail requires sidewall protection. Clear area of 10 feet required between the side wall protection.
* Access into the PAAL can only be made from 22 Street to make the turning movement required to head north to service the enclosure. The PAAL entrance is to close to 22 Street and the curb radius of 8 feet prevents the movement and is unsafe coming off 22 Street.
* The enclosure can be serviced as shown. There is a portion of the sidewalk lieing in the 14' x 40' clear area. There could be damage to the sidewalk caused by the trucks backing up after servicing the container.
05/11/2005 TIM ROWE PIMA COUNTY WASTEWATER Denied DATE: May 10, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, D05-0011 Rita Houghton Retail Center: Development Plan

CC: Craig Gross, Development Services


Please show and indicate the following:
A 10 ft wide paved path to be constructed along the length of the project’s frontage on Houghton Road.
The path is to be next to and on the east side of the scenic corridor buffer.
Indicate path specifications are: 2" asphalt with 6" thickened edges. Asphalt path is over 4" compacted ABC. The path should be consistent with the path segment under construction at the northwest corner of Rita Rd. and Houghton Rd.
The path will be ADA accessible.
Trees planted a maximum of 25 ft apart to provide shade to the path.
A removable bollard placed in the center of the path may be required at roadway crossings.
Curb ramps for the paved path at roadway crossings should be at least 10 ft wide.
All drainages crossing the path shall be below ground.
The path design and construction shall be approved by the Parks and Recreation Department



Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
05/13/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D05-0014 Oasis Bottled Water 05/12/05

( ) Tentative Plat
() Development Plan
() Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: C9-04-20

NEIGHBORHOOD PLAN: Greater South Park Area Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: May 25, 2005

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
( ) Tentative Plat
() Development Plan
() Landscape Plan
( ) Other

REVIEWER: K. Aragonez 791-4505 DATE: 5/13/2005

Please demonstrate maneuvering ability in and out of the off-street loading space is accomplished. As required by code all maneuvering must be done onsite.

Please provide a detail of the screen wall indicating compliance to rezoning condition 8 by indicating which design treatment will be utilized.
05/25/2005 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the plans to provide canopy trees for the vehicular use areas in compliance with LUC 3.7.2.3. Every parking
space shall be located within forty (40) feet of the trunk of a canopy and one (1) canopy tree is required for each ten (10) motor vehicle parking spaces or fraction thereof.

In areas where a required landscape border falls within the vehicular use area, up to 50% of the canopy trees may be counted towards both the minimum parking lot canopy tree requirement and the landscape border canopy tree requirement.

2) Revise the plans maintain a minimum distance of two (2) feet between a PAAL and any wall per DS 3-05.2.2.B.3.

3) Revise the landscape and development plans to clearly show the heights of all screen wall segments. Currently the development plan does not match the landscape plan.

4) Revise the landscape and development plans to modfy the location of the screen wall and/or sidewalk at the southeast corner of the site to eliminate conflicts.

5) Revise the the granite placement detail to specify a 2" layer per DS 2-06.5.2.C.

6) Provide a 6' high screen wall for the loading area per LUC Table 3.7.2-I.

7) Include the CDRC case number, D05-0014 on the landscape plan.

RESUBMITTAL OF PLANS IS REQUIRED







The Native Plant Preservation Exception Application is approved.
05/25/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS
1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is April 26, 2006.

2. Remove the letter P- located in the lower right corner of sheet 1 of 3 and replace it with the assigned development plan case number D05-0014. The development plan case number and rezoning case number (C9-04-20) shall be located in the lower right corner of each sheet on all plans (development, landscape, and NPPO). (D.S. 2-05.2.1.K) (D.S. 2-05.2.2.B.2)

3. Add the land use classification proposed for this project under general note three (3). General note five (5) may not be verified for compliance until the proposed use is clearly indicated. Refer to LUC Sec. 2.7.2.2 for land use classes permitted in the I-1 zone subject to compliance with the development and compatibility criteria listed for the Development Designator indicated and to any additional conditions listed for each use. The number or letter in quotation marks following the Land Use Class refers to the Development provisions of Sec. 3.2.3 and shall be listed with the land use class and any applicable "subject to" sections of the LUC. (D.S. 2-05.2.2.B.3)


4. If applicable, all existing and proposed easements and those proposed for abandonment, must be recorded and the docket and page noted on the plan prior to final approval of the development plan. (D.S. 2-05.2.3.B) (D.S. 2-05.2.4.G)

5. Demonstrate compliance with rezoning condition number two (2): "The owner /developer shall combine the lots and provide a new legal description of the property." Provide documentation and revise plan as necessary.
Provide a copy of the recorded City of Tucson Lot Combination Covenant. You may obtain a copy of the covenant online at: http://www.ci.tucson.az.us/dsd/Lot_Combo_Declaration.pdf or you may contact me at the number below. (D.S. 2-05.2.4.A)

6. Indicate how direction of the one-way PAAL is to be designated (i.e. sign, striping) on the plan. Provide a no-entrance sign at 23rd St. egress point. Sign must be located on-site and conform to SVT regulations. (D.S. 2-05.2.4.D.3)

7. Remove all notes and lines referring to the MS&R setback and building setbacks. They are not necessary. (D.S. 2-05.2.4.I)

8. Per D.S. 2-08.4.1.A, at least one (1) sidewalk shall be provided to each street the project has frontage. Indicate the location of the striped pedestrian paths where they cross a PAAL. (D.S. 2-05.2.4.K)

9. Provide the floor area ratio (FAR) calculation. Maximum FAR allowed may not be determined until the proposed land use class is provided and explained in comment number three (3).

10. City TDOT Mapguide maps do not show Martin Street. Please verify with the City of Tucson Department of Transportation. Is access proposed from "Martin Street"?

11. Provide, as a note, the number of loading spaces required and provided. Demonstrate maneuverability. (D.S. 2-05.2.4.O)

12. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. (D.S. 2-05.2.4.P) (LUC 3.3.4)

13. One (1) van accessible parking spaces is required. The width of a van accessible aisle must be a minimum five (5) wide with a minimum eleven (11) foot wide space. The plan currently shows a four (4) foot wide aisle. (D.S. 2-05.2.4.P) (ICC/ANSI A117.1-2003 Sec. 503.3)

14. As a note, provide calculations for the number of bicycle parking spaces required (include the ratio used) and the number provided, including the Class type. (D.S. 2-05.2.4.Q)

15. A screen wall in a sight visibility triangle may not exceed 30 inches in height. Proposed screen wall is 36 inches high. (D.S. 2-05.2.4.R) (D.S. 3-01.5.1.A.1)


16. Provide a separate response letter, which addresses how all rezoning conditions have been met. (D.S. 2-05.2.4.U)

17. If applicable, provide a detail of existing and/or proposed free-standing signage including billboards and outdoor lighting.

18. Please delete general note four (4) as it is only required for subdivision plats.

19. Minimum length of a parallel parking space shall be 23 feet. (D.S. 3-05.2.1.B.2)

20. Indicate graphically location of accessible ramps.

21. All requested changes must be made to the development and landscape plans.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180.
05/26/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved > SUBJECT: OASIS BOTTLED WATER
> D05-0014
>
> Tucson Electric Power Company has reviewed and approved the development
> plan submitted for review April 28, 2005.
>
> Enclosed is a copy of a TEP facilities map showing the approximate
> location of the existing facilities.
>
> In order to apply for electric service, call the New Construction
> Department at (520) 770-2062. Submit a final set of plans including
> approved site, offsite and electrical load plans. Include a CD with the
> AutoCAD version of the plans. If easements are required, they will be
> secured by separate instrument.
>
> Liza Castillo
> Right of Way Agent
> Land Management
> Tucson Electric Power Co.
> (520) 917-8745
> lcastillo@tep.com <mailto:lcastillo@tep.com>
>
05/26/2005 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved 91 ESTIMATED DAILY TRIPS IN 24 HR PERIOD.
05/26/2005 LOREN MAKUS ENGINEERING REVIEW Denied DATE: May 26, 2005

To: Patricia Gehlen
CDRC Coordinator
FROM: Loren Makus, EIT
Engineering Division


SUBJECT: Oasis Bottled Water Expansion
Development Plan D05-0014 (First Review)
T14S, R14E, Section 19

RESUBMITTAL REQUIRED: Revised Development Plan

The Engineering Division has reviewed the Development Plan and Drainage Report for Silverbell Pavilion and does not recommend approval at this time.

Development Plan Comments:

1. Show sufficient existing and proposed grades and drainage patterns to demonstrate that water harvesting will be achieved as described in the drainage statement and as required by LUC 3.7.4.5.B. Show how that runoff from the roof and parking areas will be directed through the landscape areas to the maximum extent practicable.
2. Show a 20x30 ft pedestrian sight visibility triangle at the 22nd entrance. (DS 3-01.5.1.B.1)
3. Revise the curb and sidewalk design for the intersection of Neff and 23rd street to meet the design requirements of DS 3-01.0 including figure 6 and figure 22. The endpoints of the curve should meet the straight curbline at a tangent.
4. Add the required drainage note: "Drainage will remain in its natural state and wil not be altered, disturbed, or ovstructed other than as shown on this development plan." (DS 2-05.2.2.C.1.b)
5. Clarify the status of Martin Street. Provide recordation information for the dedication of this street section.
6. Show that the loading zone and solid waste container can be accessed by the appropriate design vehicle. Show turning radii for access from the street to the on-site location and to the street again.

A complete grading permit submittal and Stormwater Pollution Prevention Plan will be required for this project.
If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
05/26/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved Please submit the following to the Real Estate Division:

1.) Legal description for the 25 foot radius spandrel. (Rezoning condition No. 4)

2.) Title report for subject parcel dated within 30 days.
05/26/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved Spandrel dedication has been completed, recorded in Dkt. 12625, at Pg 1580 on 8/26/05. Real Estate has no further comments.
05/26/2005 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this DP:

1. The access points shall have 18' radius curb returns. (DS 3-01.0 figure 6). Two radii are listed as 15'.

2. Show and label as to size (ie 20x110) both existing and future SVTs (DS 2-05.2.4.R). Missing far side SVTs from 2 of the access points.

3. Tucson City Code chapter 25-39 states in part "Minimum distance from end of a curb return . . . 4 feet OR From a curb line on a cross street at a street intersection . . . 20 feet whichever is more restrictive." The access points at 23rd Street and Neff Street appear not to meet this requirement.

4. The scale as listed in the title block does not match the scale as listed on the individual sheets.

5. List the name, ROW width, recordation data, type and dimensioned with of paving, curbs, curb cuts and sidewalks. (DS 2-05.2.2.D). Some of this information is presented but the recordation data is missing.


D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
06/01/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: May 27, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, D05-0014 Oasis Bottled Water: Development Plan

CC: Patricia Gehlen, Development Services


No comments.







Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
06/05/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

June 5, 2005

Ray Cossette
Urban Engineering, Inc.
877 S. Alvernon Way
Tucson, AZ 85711

Subject: D05-0014 Oasis Bottled Water Development Plan

Dear Ray:

Your submittal of April 28, 2005 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

10 Copies Revised Development Plan (addressing, environmental services, waste water, urban planning and design, engineering, zoning, landscaping, real estate, traffic, DSD)

4 Copies Revised Landscape Plan (zoning, engineering, landscaping, DSD)




Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 318-3808