Permit Number: D05-0012
Parcel: 103090780

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D05-0012
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/20/2005 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the development plan, sheet 2 to show a 5' high masonry wall along the west property line. LUC Table 3.7.2-I
Remove the reference to temporary chain link fencing w/ slats.
07/22/2005 JCLARK3 ENV SVCS REVIEW Approv-Cond * OK for access and Development Standards compliancd.
* Only comment noted for compliance with the landfill ordinance was that the origional comment was acknowledged. Has David Bell been comtacted and there is no landfill ordinance requirements?
07/25/2005 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D05-0012 MAJESTIC BUSINESS PARK/REVISED DEVELOPMENT PLAN
DATE: July 25, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1: Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved
Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima
County Addressing prior to assignment of addresses.

2: All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.














jg
07/30/2005 DAN CASTRO ZONING REVIEW Approv-Cond The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

1.
Provide a copy of the signed, notarized, and recorded City of Tucson Lot Combination Covenant.

2.
Class 2 bicycle rack near the southeast corner of the proposed building is located on the adjacent property. Revise the plan to show required bicycle parking located on-site.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180.
08/03/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond TO: Patricia Gehlen; CDRC Coordinator
SUBJECT: Majestic Business Park lots 2 and 3 Development Plan resubmittal Engineering Review
LOCATION: T13S R13E Section 28
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: D05-0012

SUMMARY: The revised Development Plan, Landscape Plan, and revised Drainage Report were received by CDRC on July 19, 2005. Engineering has reviewed the received items and recommends approval of the Development Plan with the following conditions. The Drainage Report was reviewed for Development Plan purposes only.

DEVELOPMENT PLAN CONDITIONS:
1) City of Tucson Development Standards (DS) Section No. 10-02.2.3.1.6.C: Regarding the proposed drainageway address the following:
a) Add note/label on a Development Plan sheet who the responsible party for the drainage improvements.
b) To the Drainage Report's drainageway maintenance checklist, add recommendations for fixing the problem conditions and also provide for a schedule for drainage maintenance.
2) DS Sec.2-05.2.1.K & 2.B.8 & 2.B.9: Provide copy of document for the rezoning condition item 2.
3) DS Sec.10-02.2.3.1.3.A.2: Provide a statement in the Drainage Report that reflects rezoning condition item 1.B(1).
4) DS Sec.10-02.2.3.1.2.D: Regarding the drainage assumptions and data that you excerpt for use in this report, insert a statement in the Drainage Report stating that you agree with the data and results used from the previous reports.

Resubmittal is required. The next submittal should address all the above conditions. Submit revised Drainage Report and the revised Development Plan. If you have questions or would like to set up a meeting, call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
08/04/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this DP.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
08/08/2005 CRAIG GROSS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 1, 2005

Jeff Stanley
Stanley Engineering
3409 East Green Ridge
Tucson, AZ 85741

Subject: D05-0012 Majestic Business Park Lots 2 & 3 Development Plan

Dear Jeff:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per Community Planning, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blueline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from Reproductions, Inc. and billed to you. If you do not already have an account at Reproductions, Inc., please contact them at (520) 622-7747 to arrange for payment. If you are located in Tucson, Reproductions, Inc. will deliver the mylar and two (2) blueline copies to your office. If you are out of town you will need to arrange to pick them up at the CDRC office of Development Services.

Should you have any questions, please call me at 791-5608.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/


Via fax: 299-8777