Permit Number: D05-0011
Parcel: 14118001E

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D05-0011
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/10/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Craig Gross DATE: June 10, 2005
Planning Administrator
SUBJECT: 8210 S. Houghton Rd CDRC
Development Plan D05-0011 (Second Review)
T15S, R150E, Section 26

RESUBMITTAL REQUIRED: Development Plan.

The Development Plan (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Please provide property description per D.S. 2-02.2.1.3.
3. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. List which datum is being used, ie: NGVD 1929 or NAVD 1988. Per pervious comment.
4. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The approaches to the refuse container between the buildings at the East property line cannot travel over the property lines. Per previous comment.
5. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. The contours are labeled sufficiently, however check the contour labels at the North side of the property where two contour labels have the same label of 2990.

Drainage Report:
1. The Drainage Report is accepted for Development plan purposes only

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/8210 S. Houghton Rd CDRC2
06/14/2005 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the landscape plan and development to remove the PROPOSED monument sign from the 30' scenic route buffer area. LUC 2.8.2.4
SEE KEYNOTE 22 ON SHEET DP2

2) Submit photos of the site with the SCZ application and a list of plants indigenous to the site or surrounding area.
Additional comments may apply.

3) Revise the lower right corner of sheet L2. The owner information and the SVT information are printed in the same location making the text difficult to read.

4) Revise the MS&R right-of-way dimension string for Houghton Road on sheet N-1 (Lots 1 & 2) to match the landscape plan and other documents.
06/14/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approved June 13, 2005

TO: David Tannous
Sayler-Brown Bolduc Architects L.L.C.

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Rita Houghton Retail Center, Lots 1 & 2
Development Plan – 2nd Submittal
D05-0011


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project is hereby approved as submitted.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
06/20/2005 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
D05-011
Rita Houghton Retail Center
Development Plan

TRANSMITTAL: June 21, 2005
DUE DATE: June 21, 2005

1. A Scenic Corridor Zone (SCZ) application has been submitted and must be approved prior to development plan approval. Once approved, include the SCZ case number (SCZ-05-10), date of approval, approved colors and conditions in the general notes. General note 26 will need to be corrected to reflect the new SCZ case and because there is no sheet DP3 included with this development plan. Also, remove the reference to "200' Scenic Setback" in the legend on sheet 2 of 4 as the requirement is 400' and keynote #8 describes this setback line adequately.
DS 2-05.2.2.B.10

2. For clarity, label each building by number in the parking calculation as per the map. The uses and square footages listed on the map do not match those shown in the parking calculations. For example Bldg. 3 is shown as 80 feet by 65 feet (calculates to 5,200 square feet as stated in the parking calculations) but labeled as 6,400 square feet with uses labeled as retail/restaurant/personal service on the drawing, but office/retail/restaurant uses listed in the parking calculations. If the dimension along the north side of building 3 is intended to read "80 feet, revise accordingly. Restaurant uses are parked at 1 vehicle space per 100 square feet but the parking calculation reads 1 per 200 square feet for the 5,200 square foot building. The pad 1 parking calculation states that the principal use is to be restaurant, parked at 1 space per 100 square feet but the parking calculation reads 1 per 200 square feet. Make sure all proposed uses and square footages are stated correctly on the drawing and are consistent with those listed in the parking calculations.
LUC 3.3.5.1
LUC 3.3.4
DS 2-05.2.4.P

3. Bicycle parking is based on the uses proposed and the number of vehicle parking spaces provided. Revise the bicycle parking calculation to be based on 8 percent of the total vehicle spaces provided (8% x 242 spaces = 19 bicycle parking spaces required. Label the required bicycle parking spaces for Pad #1and show their location on the plan.
DS 2-05.2.4.Q
DS 2-09.6.0

4. Provide copies of cross access agreement for the property to the west for the vehicular access and trash pick up areas. Add the recordation information to the plan.

5. The future 20' x 30' far side pedestrian sight visibility triangle at the entry drive along Rita Road is drawn incorrectly. Revise to reflect the true dimensions. DS 2-05.2.4.R

6. Revise the 75' dimension label for Rita Road and the 100' dimension label for Houghton Road to specify that these are the ½ right-of-way dimensions.
DS 2-05.2.4.E

7. The parking count numbers in the area of the handicapped spaces located in front of buildings 1 and 2 indicate "5" and "6" spaces but 6 and 7 spaces respectively are shown on the drawing. The h/c parking calculation indicates 17 spaces are provided but only 14 are shown on the drawing. The parking calcs. indicate 242 spaces are provided but the total parking shown on the drawing is 243. Revise plan to be consistent.
DS 2-05.2.4.P

8. The calculations indicate that 3 loading zones are required and provided but only 2 are shown on the drawing. At least one loading zone must be provided for the Pad #1 building. Label and dimension this required loading zone on the plan. LUC 3.4.4.1.B.2

9. This property has been split in the last 20 years and a new interior lot line is shown running east-to-west through the property. Provide copies of approved lot split documents. If the lot split has not been approved and the number of splits in the last twenty years has exceeded the maximum allowed (2 splits) for unsubdivided property, an approved subdivision plat will be required prior to the development plan approval.
LUC 3.2.6.5
DS 2-05.2.4.I

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan, subdivision plat, recorded cross access agreement.
06/21/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D05-0011 Rita Houghton Retail Center 06/21/05

() Tentative Plat
(x) Development Plan
(x) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: N/A

NEIGHBORHOOD PLAN: Esmond Station

GATEWAY/SCENIC ROUTE: Scenic Route

COMMENTS DUE BY: 06/21/05

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(x) No Additional Comments - Complies With Planning Comments Submitted on: 04/28/06
( ) Resubmittal Required:
() Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Other

REVIEWER: Eric Anderson 791-4505 DATE: 06/17/05
06/22/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this DP.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
06/28/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Denied DATE: June 24, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, D05-0011 Rita Houghton Retail Center: Development Plan Resub. 6/7/05

CC: Craig Gross, Development Services


Denied. Previous comments have not been addressed.



Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
07/05/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 5, 2005

Thomas Sayler Brown
SBBA Architects
1001 North Alvernon Way
Tucson, AZ 85711

Subject: D05-0011 Rita Houghton Retail Center Development Plan

Dear Thomas:

Your submittal of June 7, 2005 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

5 Copies Revised Development Plan (Parks and Recreation, engineering, landscaping, zoning, DSD)

5 Copies Revised Landscape Plan (Parks and Recreation, engineering, zoning, landscaping, DSD)




Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager