Permit Number: D04-0037
Parcel: 132169280

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D04-0037
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/15/2005 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D04-0037 ANDREW LAUREN GRANITE / REVISED DEVELOPMENT PLAN
DATE: MARCH 14, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1. Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
03/16/2005 MARILYN KALTHOFF PIMA COUNTY WASTEWATER Approv-Cond March 16, 2005

TO: Jeff Stanley, P.E.
Entranco

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Andrew Lauren Granite
Development Plan - 2nd Submittal
D04-0037

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. SHEET 1. The previous wastewater review letter erroneously referenced the Pima County Code. Please revise General Note 20 to read as shown below and fill in the blanks appropriately

THIS PROJECT HAS ____ PROPOSED AND ____ EXISTING WASTEWATER FIXTURE UNIT EQUIVALENTS, PER TABLE 13.20.045(E)(1) IN PIMA COUNTY CODE 13.20.045(E).

2. SHEET 1. The previous wastewater review letter erroneously indicated to ad a general note that did not apply for this project. Please replace General Note 15 with this one below.

THE ON-SITE SEWERS ARE EXISTING AND PRIVATE. NO NEW SEWERS ARE PROPOSED.

3. SHEET 1. Add the following General Note

MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWER TO ITS POINT OF CONNECTION TO THE PUBLIC SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER.

4. Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the tentative plat. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Department of Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
03/19/2005 PETER MCLAUGHLIN ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
D04-037
Andrew Lauren Granite
Apache Business Park

TRANSMITTAL: March 19, 2005
DUE DATE: March 26, 2005

The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

1. Place the development plan number (D04-037) and rezoning case (C9-81-60) on the second sheet of the development plan as was done for the first sheet. Provide sheet numbers in the blanks (i.e. sheets 1of 2 and 2 of 2) for ease of reference.
DS 2-05.2.1.K

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
03/23/2005 JCLARK3 ENV SVCS REVIEW Approved
03/24/2005 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: ANDREW LAUREN GRANITE
D04-0037

Tucson Electric Power Company has reviewed and approved the development plan
dated March 10, 2005.

Please call me at (520) 917-8745, should you have any questions.



Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8745
Cell Phone: (520) 904-2668
Fax: (520) 917-8700
03/25/2005 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Based on the expansion of site area the entire property (Lots 15 & 16) is subject to the current provisions LUC 3.7, with limited exceptions. Include the existing and/or proposed landscaping for LOT 16.

2) Submit an irrigation plan. No sheet L-2 was received.

3) Revise the landscape and development plans for consistency regarding the removal and construction of walls along Fair Street. Show the new wall for Lot 15 on the landscape plan. Clarify the location of existing and proposed walls for Lot 16 on both plans.
04/04/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond TO: Craig Gross; CDRC Coordinator
SUBJECT: Andrew Lauren Development Plan 2nd Submittal Engineering Review
LOCATION: T14S R14E Section 31
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: D04-0037

SUMMARY: The revised Development Plan, Landscape Plan, and Drainage Report were received by Engineering on December 15, 2004. Engineering has reviewed the received items and does not recommend approval of the Development Plan or the Drainage Report at this time. The Drainage Report was reviewed for Development Plan purposes only.

DEVELOPMENT PLAN CONDITIONS OF APPROVAL:
1) City of Tucson Development Standards (DS) Section No.2-05.2.4.I: Provide a complete copy of the soils report, as a few pages are missing.
2) DS Sec.2-05.2.1.K & 2.B.8 & 2.B.9: Regarding rezoning case number C9-81-60, provide a copy of the letter of request per rezoning condition item G.

These conditions shall be addressed at mylar submittal. If you have questions, call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
04/04/2005 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed