Permit Number: D04-0028
Parcel: 136261290

Review Status: Completed

Review Details: RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D04-0028
Review Name: RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/17/2004 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: Safeway Plaza, Pad 3
D04-0028

Tucson Electric Power Company has reviewed and approved the development plan
dated September 9, 2004.

Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8745
Cell Phone: (520) 904-2668
Fax: (520) 917-8700
09/17/2004 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D04-0028 SAFEWAY PLAZA PAD 3 / REVISED DEVELOPMENT PLAN
DATE: SEPTEMBER 13, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1: Delete Buildings 7 from all Storage Unit Bldgs. Per the original development plan
they are numbered Bldg 1 thru Bldg 6.
09/17/2004 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D04-0028 SAFEWAY PLAZA PAD 3 / REVISED DEVELOPMENT PLAN
DATE: OCTOBER 5, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

Approved on condition that storage building numbers are corrected on Mylar.


NOTE:

1. Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
09/21/2004 JCLARK3 ENV SVCS REVIEW Approv-Cond * Responded by letter to Stantec, the consultant, for the project. The single enclosure can be serviced as designed for pad three.
* The comments addressed in the letter are as follows:
* Resturants usually have a recycling dumpster along with a garbage dumpster.
* One dumpster for three bussinesses (especially since two are fast food bussinesses) does not seem sufficient.
* Sent sketches of possible solutions for the consultant to consider. There are no provisions in the Development Standards so stanting what should be provided. Single dumpster can be serviced as designed.
09/23/2004 PETER MCLAUGHLIN ZONING REVIEW Approved CDRC TRANSMITTAL


TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
D04-028
Safeway Plaza Pad 3
Development Plan

TRANSMITTAL: September 23, 2004
DUE DATE: September 24, 2004

The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

Please have the applicant submit sign-off copies of the development and landscape plans for approval



If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
10/07/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed
10/07/2004 MARILYN KALTHOFF PIMA COUNTY WASTEWATER Approved October 7, 2004

TO: Paul Keesler, P.E., Stantec Consulting, Inc.

THRU:


FROM: ____________________________________
Tim Rowe, P.E. representing the Pima County
Departments of Wastewater Management and Environmental Quality

SUBJECT: Safeway Plaza Pad 3
- Submittal
D04-0028


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Sheets 6 & 11: The proposed private sewers for Pad 3 may not have a design flow of 3000 gallons per day or more, but they are carrying the wastewater from two grease interceptors. One can expect grease to build-up over time in the area where the proposed private sewer lines connect to the existing private sewer line, even with proper maintenance of the grease interceptors.

For greater ease and flexibility during maintenance of the proposed and existing private sewer lines, we recommend that the proposed private sewer line be connected to the existing private sewer line via a manhole rather than a cleanout, although this is not be required by any of the applicable codes and regulations. This is not a requirement, however, it is only a recommendation. No change is required to the development plan.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.



If you wish to discuss the above comments, please contact me at the phone number provided above, under my signature.

Copy: Project