Permit Number: D04-0027
Parcel: 11449030A

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D04-0027
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/30/2004 JIM EGAN COT NON-DSD FIRE Denied 1. Minimum fire access roadway width is 20 feet. Remove center island at entrance or provide minimum 20 feet wide roadway width.
2. Provide a General Note stating: "Additional fire hydrants shall be provided by the Developer in accordance with the Tucson Fire Code."
3.Turnaround shall be paved.
07/01/2004 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D04-0027 RINCON MOUNTAIN PRES. CHURCH/DEVELOPMENT PLAN
DATE: 7/01/04



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Label section corners on Location Map.

Correct Woodland Ave. to Woodland Road on Location Map.

Number buildings numerically.

Revise Title Block in lower right corner. This project is not “For” ELA Architects. It is not in Bk 13, Pg 58 and the Ref: P1203-036 does not pertain to this project.
07/06/2004 PAUL MACHADO ENGINEERING REVIEW Denied To: Craig Gross DATE: July 6, 2004
Planning Administrator

SUBJECT: 8445 E Tanque Verde Rd.,
Development Plan D04-0027 (First Review)
T15S, R13E, Section 33

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
3. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
4. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
5. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DP. See comment 3 of the DR comments.
6. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
7. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
8. Show Development plan number (D04-0027) on all sheets per D.S. 2-02.2.1.29.
9. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Please use a 30° degree angle instead of the 45° used for the dumpster enclosure. The clear space for the dumpster is 10' from bollard to bollard in the interior. Please show a detail of the dumpster enclosure. For more information contact John Clark of Environmental Services @ 791-5543.
10. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
11. Minimum paving per L.U.C 3.3.7.3 is required in the turnaround.
12. Please list area of total disturbance and show grading limits.
13. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
14. It is not clear whether extruded curb is used in the right-of-way, however only vertical curb is allowed in the right-of-way. Please call this out on the plans.
15. 5' sidewalks are required along the frontage property per D.S. 3-01. 3.3.A.
16. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
17. The rip-rap keynote 17 calls out detail 5 on sht. 2, however detail 5 is parking space standard. Please show the rip-rap detail.
18. Please show a Det/Ret basin detail calling out all dimensions. This aids with inspection as well as in construction.
19. A Stormwater pollution prevention plan is required with the Grading Plan submittal. Contact Paul P. Machado at 791-5550 x1193 for additional information.
Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. The DR is accepted for Development Plan purposes only.
3. Please edit the basin and drainage way maintenance to read as follows:
Detention/Retention basin Inspection and Maintenance note:

A. The responsibility of operating and maintaining a local detention basin rests with the owner of the facility.

B. (a.) That the owner(s) shall be solely responsible for, operation, maintenance and liability for the drainage basin(s); (b.) That the owner(s) shall have an Arizona registered professional engineer prepare a certified inspection report for the drainage and detention/retention facilities at least once a year, and that these regular inspection reports will be on file with the owner for review by city staff, upon written request; (c.) That city staff may periodically inspect the drainage and detention/retention facilities to verify scheduled and unscheduled maintenance activities are being performed adequately; and (d) That the owners(s) agree to reimburse the city for any and all costs associated with maintaining the drainage and detention/retention facilities, should the city find the owner(s) deficient in their obligation to adequately operate and maintain their facilities.
4. Please include a detail of the Det/Ret basin in the drainage report w/ dimensions.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/8445 E Tanque Verde Rd CDRC
07/12/2004 JCLARK3 ENV SVCS REVIEW Denied No known landfills within 1000'of this development.
Turning radius of collection vehicle is in conflict with the west parking along the PAAL. Recommend that the enclosure bedesigned at a 30 degree angle to the PAAL or the enclosure be designed parallel with the PAAL so that it can be serviced from the parking lot PAAL from the west. (Concerned with the turning around of the vehicle since the turnaround to the north will not be constructed at this time.)
No provisions mentioned or provided for recycling.
07/14/2004 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Transportation Information for Rezoning,
Subdivision and Development Review Requests
File Number Description Date Reviewed
E
Pima Association of Governments
Transportation Planning Division
177 N. Church Avenue, Suite 405
Tucson, AZ 85701
Phone: (520) 792-1093
Fax: (520) 792-9151
www.pagnet.org
D04-0027 Rincon Mountain Pres. Church 7/8/2004
1. Nearest Existing or Planned Major Street
2. Is improvement planned as part of the 5-Year Transportation Improvement Program
Planned Action:
STREET IDENTIFICATION
3. Existing Daily Volume – Based on Average Daily Traffic
4. Existing Daily Capacity- Level of Service “E”
5. Existing Number of Lanes
9. Estimated Traffic Generation for Proposed Development
(Expressed in Average 24 Hr. Vehicle Trips)
8. Future Number of Lanes
TRANSIT AND BIKEWAYS CONSIDERATIONS
10. Present Bus Service (Route, Frequency, Distance)
11. Existing or Planned Bikeway
Remarks:
Street Number 1 Street Number 2
Year Year
Planned Action:
VOLUME/CAPACITY/TRAFFIC GENERATION CONSIDERATIONS
6. Future Daily Volume - Adopted Plan System Completed
7. Future Daily Capacity - Level of Service “E”
Tanque Verde Rd (Pantano to Bear Canyon)
No 0
36,200
63,000
4
63,000
44,893
4
626
Route 81, Express no weekend service, 0
miles
Bike route with striped shoulder
0
0
0
0
0
0
0
07/16/2004 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the plans to include paving and curbing for the truck turn around. DS 3-01.5.0

2) Revise the landscape plan to show the extent of phase one development and any future development. DS 2-07.2.0
Show the NUOS areas, landscaping required for retention basins, the area of the truck turn around, any protected plants to be preserved in the vicinity.

3) An Environmental Resource Report is required for projects
submitted under the NPP set-aside methodology. LUC 3.8.6.4.A

4) Per LUC 3.8.6.4.B "The set aside area shall consist of the area(s) with the highest resource value as determined
by the ERR" The watercourse and accompanying mesquite bosque should be set-aside. Refer to the Critical and Sensitive Biological Communities Map and the Sonoran Desert Conservation Plan Conservation Lands System Map. Both document the bosque as an important riparian area. The project design may require modification.

5) Clearly delineate any NUOS areas clearly on the development plan. LUC 3.8.6.4
The NUOS area recording information is to included on the development plan.

6) Only permitted improvements per LUC 3.7.5.2.C are allowed within the scenic route buffer area. The proposed sign is not a listed as permitted improvement. See also Sign
Section comments.

7) Revise scenic corridor zone note 2 on sheet L-1 to reference note 7, rather than 4.

8) Revise the landscape plan to comply with SCZ note 4 on sheet L-1.

9) Revise note 28 on sheet 1 of the development plan to reference any specific variances approved. DS 2-07.2.0

10) Revise the landscape and native plant preservation plan to locate the limits of disturbance/grading.

RESUBMITTAL OF ALL PLANS IS REQUIRED. IN ADDITION, AN ENVIRONMENTAL RESOURCE REPORT IS REQUIRED.
07/21/2004 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Approv-Cond From: Robert E. Flynt, Senior Civil Engineering Assistant
Pima County Development Services

On hehalf of PDEQ, the Development Plan has been reviewed for conformance with Department of Environmental Quality requirements. Please note the following comments:

1. Add General Note 29 as follows: The proposed development will be served by an on-site sewage disposal system. Prior to construction, a Notice of Intent to Discharge shall be submitted to PDEQ in order to receive Construction Authorization.

2. Add General Note 30 as follows: The on-site disposal system shall be designed and constructed in accordance with Arizona Administrative Code Title 18 Chapter 9.

Subject to the above, the Development Plan is approved. If you wish to discuss the above comments, please contact me at 740-6502.

The Department's Air Quality Control District requires that air quality activity permits be secured by the developer or prime contractor before constructing, operating or engaging in an activity which may cause or contribute to air pollution.
07/26/2004 JIM STOYANOFF COT NON-DSD REAL ESTATE Approved no comments/objections
07/27/2004 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: Rincon Mountain Presbyterian Church
D04-0027

Tucson Electric Power Company has reviewed and approved the development plan submitted for review June 24, 2004.

Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. There are existing underground facilities outside of the project area to the south that my be in conflict with off-site improvements. All cost associated with the relocation of the facilities in conflict will be billable to the developer.

Application for electrical service should be made by contacting the New Construction Department at (520) 770-2062. If easements are required, they will be secured by separate instrument. Two sets of site plans, electrical load plans and off-site improvement plans are required for a preliminary electrical design. These plans should be sent in a minimum of ten (10) weeks prior to requiring service.

Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8479
Cell Phone/Pager: (520) 904-2668
Fax: (520) 917-8400
07/27/2004 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC Review Comments

TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
D04-027
Rincon Mountain Presbyterian Church
8445 E. Tanque Verde Road
Development Plan

TRANSMITTAL: 7-27-04
DUE DATE: 7-27-04


1. LUC Section 5.3.8.2 permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for full CDRC review. The one year expiration date for this development plan is June 28, 2005.

2. Place the development plan number (D04-027) on each sheet of the d.p., landscape plan and NPPO plan in the lower right hand corner near the title block. Also, place the SCZ case number (refer to comment 6), on each sheet of the site plan, landscape plan and NPPO plans in the lower right hand corner near the title block. Although this plan was submitted as a development plan, it does not contain many of the elements, calculations, general notes etc. required. Please refer to DS 2-05 for development plan standards.
DS 2-05.2.2.B.2

3. Add the adjacent zoning to the plan drawing. DS 2-05.2.4.B

4. Add the phone number of the property owner.
DS 2-05.2.2.A.1

5. Revise the location/vicinity map on sheet C-1to cover approximately 1 square mile and to include labeled section, township and range corners. Enlarge the text in the location map to be legible minimum of 12 point (see comment 6 below).
DS 2-05.2.1.D
DS 2-05.2.1.C

6. This project area is within the 400-foot Scenic Corridor for Tanque Verde Road. A Scenic Corridor Zone (SCZ) application must be approved prior to development plan approval. Include the SCZ case number , date of approval, approved colors and conditions in the general notes. DS 2-05.2.2.B.10

7. Add and dimension the 400' Scenic Corridor line, along with the 30' natural buffer, to the drawing. Provide a calculation of view corridors per LUC 2.8.2.6.B. LUC 2.8.2.3, 2.8.2.4, & 2.8.2.6

8. All lettering and dimensions shall be a minimum of twelve point (0.12") in size for microfilming/archiving purposes. Revise text which does not meet this minimum standard. More comments may be necessary once text is enlarged.
DS 2-05.2.1.C

9. Revise the title block to indicate that the development plan is for Rincon Mountain Presbyterian Church. DS 2-05.2.1.G

10. Add the annexation case number (C15-89-2) to the lower right hand corner of the plan near the title block. List the conditions of annexation as a general note. DS 2-05.2.2.B.7

11. Add vehicle parking calculations to the plan stating the number of standard and handicap parking spaces required and provided. Include the parking ratios used in the calculation. Also, add a fully dimensioned parking detail showing the width and length of standard vehicle parking spaces. Dimension the wheelstops at 2-½ feet from the front of parking spaces. DS 2-05.2.4.P
DS 3-05.2.3.C.2

12. Add bicycle parking calculations to the plan stating the number of class 1 and class 2 bike spaces required and provided. Show location of class 1 and class 2 spaces on the plan drawing, fully dimensioned per DS 2-09.
DS 2-05.2.4.Q
DS 2-09

13. Sidewalks within the project must be physically separated from vehicular travel lanes and parking spaces by means of curbing, except at crosswalks. A pedestrian circulation system may not contain a continuous crosswalk extending through the parking lot. Also, the pedestrian sidewalk must connect all areas of the development and must provide connections between the building to sidewalks along the adjacent street frontages. Refer to sidewalk locational requirements in Development Standards Sec 2-08.4.
DS 2-08.4.1

14. Dimension completely the width of pedestrian circulation system on the drawing. DS 2-05.2.4.K

15. Dimension required and proposed building setbacks on the plan. Building setbacks to adjacent SR zoned property lines are required to be 25 feet. Building setbacks to Tanque Verde Road (MS&R) are required to be the greater of 21 feet and the height of exterior building wall measured from back of future curb location. DS 2-05.2.4.I
LUC 3.2.6.4
LUC 3.2.6.5

16. Correct the development designator to read "6" for the religious use.
LUC 2.2.4.2.C.4

17. Provide a loading zone calculation detailing the number of loading zones required and provided with each phase of development. DS 2-05.2.4.O

18. Dimension the buildings and add the proposed building heights to the drawing along each wall of the buildings.
DS 2-05.2.4.N

19. Because the project is phased, provide a future plans for each phase of development showing all calculations (FAR, vehicle parking, bicycle parking, loading zones, etc), setbacks, heights and dimensions to indicate that the future phase complies with all requirements separately. Plans must show how site will meet code in the future upon completion of each phase.
DS 2-05.2.5.C

20. Label and dimension any existing or proposed easements and add their recordation information to the site plan.
DS 2-05.2.3.B
DS 2-05.2.4.G

21. Add existing and future sight visibility triangles at the entrance drive from Tanque Verde Road. Keynote 23 is used twice in the keynote list to indicate SVT's. Are the indicated SVT's future or existing? DS 3-01.5.1.B.1

22. Add a general note which reads "Existing zoning is SR". Refer to DS 2-05 for all standard required general notes and their format.
DS 2-05.2.2.B.1

23. Add a general note stating that the project meets the criteria for LUC Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone. Place all other required general notes. Refer to DS 2-05.2.2.
DS 2-05.2.2.B.10

24. Show existing and proposed sidewalks clearly and completely along adjacent rights-of-way. Sidewalks must comply with accessibility requirements for the handicapped. Per Mayor and Council policy directive, new sidewalks along MS&R rights-of-way are to be 6-feet. DS 2-09

25. Add a Floor Area Ratio (FAR) calculation to the plan based on the gross floor area of building(s) divided by site area. Add the FAR for all phases of development (see comment 16). DS 2-05.2.4.M
DS 2-05.2.4.C

26. Provide the maximum slope of the handicap aisle and any associated ramps adjacent to the h/c vehicle parking spaces. ANS

27. See Landscape Review comments regarding Environmental Resource Zone (ERZ) submittal requirements.

28. All requested changes must be made to the Development Plan and Landscape Plan.
DS 2-07.2.1.A

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan, SCZ application.
07/27/2004 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Passed no comments provided.
07/27/2004 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D04-0027 Rincon Mountain Pres. Church 07/27/04

() Tentative Plat
(XXXX) Development Plan
() Landscape Plan
(XXXX) Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: N/A

GATEWAY/SCENIC ROUTE: SCENIC

COMMENTS DUE BY: 07/26/04

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(xxxxx) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: DCE 791-4505 DATE: 7/16/04
07/29/2004 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this DP:

1. General Note 1 on sheet 1 of 2, the current edition of the SSPI is 2003.

2. General Note 11 on sheet 1 of 2, the title is the "Manual ON Uniform Traffic Control Devices", not the Manual of...

3. Show and label as to size (ie 20x345) both existing and future SVTs (DS 2-05.2.4.R)

4. Show and label both existing and future ROW (DS 2-05.2.3.C, 2-05.2.4.E, 2-05.2.4.F)




D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
07/29/2004 GLENN HICKS COT NON-DSD PARKS & RECREATION Approv-Cond DATE: July 29, 2004

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, D04-0027 Rincon Mountain Pres. Church: Development Plan

CC: Craig Gross, Development Services

Conditional approval is granted provided the following conditions are met:

Sabino Creek is a trail route designated by the Eastern Pima County Trail System Master Plan. A public, non-motorized trail corridor shall be dedicated by fee or easement to the City of Tucson for Sabino Creek Trail #45. The trail corridor shall be a minimum of 75 ft in width measured southwest from the top of the bank of Sabino Creek.

The area of the property designated Critical and Sensitive Biological Communities(Shaw, 1986) shall be preserved.

The above conditions are in keeping with the City of Tucson General Plan, Element 14: Environmental Planning and Conservation, Policies 1, 3 and Element 10: Parks Recreation, Open Space and Trails, Policies 8, 9, 10, 11.


Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
08/06/2004 TIM ROWE PIMA COUNTY WASTEWATER Approved Rincon Mountain Presbyterian Church
D04-0027


On behalf of PDEQ, the development plan has been reviewed for conformance with Department of Environmental Quality requirements. Please note the following comments:

1. Add General Note 29 as follows: The proposed development will be served by an on-site sewage disposal system. Prior to construction, a Notice of Intent to Discharge shall be submitted to PDEQ in order to receive Construction Authorization.

2. Add General Note 30 as follows: The on-site disposal system shall be designed and constructed in accordance with Arizona Administrative Code Title 18 Chapter 9.

Subject to the above, the development plan is approved. If you wish to discuss the above comments, please contact me at 740-6502.

The Department's Air Quality Control District requires that air quality activity permits be secured by the developer or prime contractor before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

Robert E. Flynn, Senior Civil Engineering Assistant
Pima County Development Services
08/06/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed