Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/03/2004 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the plans to comply with LUC 3.7.2.2. Include a calculation for oasis areas per DS 2-07.2.2.A.2.b. Include planting areas for Ulmus parviflora.

THE NATIVE PLANT PRESERVATION APPLICATION FOR EXCEPTION IS APPROVED.

RESUBMITTAL OF THE LANDSCAPE AND DEVELOPMENT PLAN IS REQUIRED.
08/05/2004 MARILYN KALTHOFF PIMA COUNTY WASTEWATER Approv-Cond August 5, 2004

TO: Bruce Call, Bruce R. Call, AECM

THRU:


FROM: ____________________________________
representing the Pima County
Departments of Wastewater Management and Environmental Quality

SUBJECT: Rita Ranch LDS Church
- Submittal
D04-0017


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Show the length and slope of the proposed building connection sewer.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you wish to discuss the above comments, please contact me at the phone number provided above, under my signature.

Copy: Project
08/06/2004 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: PIMA COUNTY SUBDIVISION COORDINATOR
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D04-0017 RITA RANCH LDS CHURCH / REVISED DEVELOPMENT PLAN
DATE: August 5, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
08/13/2004 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
D04-017
Rita Ranch LDS Church
Development Plan

TRANSMITTAL: August 13, 2004
DUE DATE: August 16, 2004


1. It is acknowledged that a Board of Adjustment variance is being sought for the steeple height, which is proposed at 67 feet. The maximum allowed height for a church in the C-2 zone is 40 feet, while design elements such as steeples may be up to 50 feet (10 feet above allowed structure height). Once submitted variance application for case #C10-04-25 is approved, add date of approval and conditions to general note 17. Also, add the case number in the lower right hand corner in or near the title block.
LUC 3.2.3.2.B
LUC 3.2.7.3.A
DS 2-05.2.2.B.6
If you have any questions about this transmittal, please call Peter McLaughlin, (520)791-5608.
08/16/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed
08/16/2004 PAUL MACHADO ENGINEERING REVIEW Denied To: Craig Gross DATE: August 16, 2004
Planning Administrator
SUBJECT: LDS church in Rita Ranch, 8285 E. Rees Loop
Development Plan D04-0017 (Second Review)
T15S, R15E, Section 26

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.


Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. A separate grading submittal is required. Sheet C1 is being reviewed for the Development Plan purposes only. A separate submittal and permit is required. Please contact the CDRC office for this and other submittal requirements.
3. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice. Using a length of 90' in lieu of the 230' because the sidewalk (or weir) is separated into 3 sections on one side and 4 sections on the other side, this results in a depth of 6". Also the C=3 coefficient should be 2.6 in the equation per COT standards, this also raises the depth of flow. Please revise. Per pervious comment.

Drainage Report:
1. The Drainage Report is accepted for Development plan purposes only. Additional comments may be made at the Grading plan review stage.
2. A manhole is required for storm drains in excess of 45" in diameter every 500' per S.M.D.D.F.M. Chap. 10.9.1.8. Although a COT Type 4 CB is being utilized, the manhole requirement is still valid. Please revise. Per previous comment.




Stormwater pollution prevention plan:
1. The SWPPP is accepted for Development plan purposes only. Additional comments will be made during the Grading plan review stage.
2. 3 Copies of the SWPPP and Grading plan are required for the final submittal.


If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/8285 E. Rees Loop CDRC 2