Permit Number: D04-0010
Parcel: 12414115A

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D04-0010
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/29/2004 JIM EGAN COT NON-DSD FIRE Approved The Development Plan is approved March 29, 2004.
04/02/2004 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
D04-0010
DELPH ENGINEERING INC
HIGHLANDS FREE SCHOOL
04/07/2004 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: HIGHLANDS FREE SCHOOL
D040010

Tucson Electric Power Company has reviewed and approved the development plan dated March 25, 2004. As you are aware, there are existing electrical facilities within the boundaries of this project. TEP must have permanent access to our facilities within the gated area. All relocation costs will be billable to the developer.

Please submit a final set of plans including electrical load plans, to determine how TEP will serve this commercial development. If easements are required, they will be secured by separate instrument. Submit your plans a minimum of eight (8) weeks prior to requiring service.

Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8479
Pager: (520) 218-6565
Fax: (520) 917-8400
04/20/2004 FRODRIG2 COT NON-DSD ENVIRONMENTAL SERVICES Denied Environmentas Services Comments:
* Commercial Development shall provide for collection per Section 6-01.3.0 of the Development Standards.
* Provided plan does not show on site storage for centralized collection or enclosure for such service.
04/21/2004 TIM ROWE PIMA COUNTY WASTEWATER Denied April 16, 2004

TO: Kent A. Delph
Delph Engineering, Inc.

THRU: Craig Gross
City of Tucson Development Services Department

FROM: Dickie Fernández, E.I.T.
Development Review Division (Wastewater)

SUBJECT: Highlands Free School
Development Plan – 1st Submittal
D04-0010

The above-referenced project has been reviewed on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

This project will be tributary to the Roger Road Wastewater Treatment Facility via the Aviation Corridor to Santa Cruz Interceptor. The amount of available treatment and conveyance capacity in these facilities for proposed development is extremely limited, but there is sufficient treatment and conveyance capacity in these facilities for this extremely small project at this time. The additional flow from this proposed project would not cause an flow of effluent quality limits to be exceeded. This response is not to be construed as a commitment for treatment or conveyance capacity allocation, but rather an analysis of the existing sewerage system as of this date.

Based on our evaluation, this project would qualify for Non-Participating sewer connection fee rates.

ALL SHEETS. Add the project number, D04-0010, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Sheets 2: Show all existing public sewer lines on, and within 100’ of, the boundaries of the development. Label each existing public sewer line with its size and plan number.

Sheet 2: Show the existing private sewer lines serving the existing building and how it connects to the public sewer network.
Sheet 2: Show how the proposed private sewer will connect to the existing public or private sewer lines.

Sheet 2: Use different linetypes for the public and private sewer lines, so that they can be readily told apart. Show the proposed private sewer line more boldly than the existing public and private sewer lines.

Sheet 1: Revise the legend to show and describe the different linetypes (and line weights) used to depict the existing public sewers, existing private sewers and proposed private sewers.

A complete set of revised bluelines, and a response letter, addressing these comments is required. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter. If the number of revised sheets changes, please adjust the review fee accordingly.

If you wish to discuss the above comments, please contact me at 740-6947.





Dickie Fernández, E.I.T.
Development Review Division (Wastewater)

Copy: Project

DF/df
04/21/2004 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D04-0010 HIGHLANDS FREE SCHOOL/DEVELOPMENT PLAN
DATE: APRIL 21, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Correct Title Block to read: Lots 1-4, Blk 14 of Randolph Addition, Bk 5, Pg 54.

Correct Randolph to Randolph Addition in Legal Description.

Correct “Purposed” to “Proposed” in General Note #3.

Correct Block 13, Bk 3, Pg 12 to Block 15, Bk 5, Pg 54 on sheet 2.

Correct Highland Ave to Highland Avenue (sheets 2 and 3).

Number buildings numerically.








jg
04/23/2004 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: April 22, 2004

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, D04-0010 Highlands Free School: DP

CC: Craig Gross, Development Services


Staff has reviewed the development plan and has no comments.


Please feel free to call me at 791-4873 x 215 if you have any questions.
04/23/2004 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D04-0010 Highlands Free School 04/23/04

() Tentative Plat
(XXXX) Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: SE-03-04

NEIGHBORHOOD PLAN: Arroyo Chico

GATEWAY/SCENIC ROUTE: n/a

COMMENTS DUE BY: 04/22/04

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
(XXXX) Resubmittal Required:
() Tentative Plat
(XXXX) Development Plan
(XXXX) Landscape Plan
(XXXX) Other – Sign detail, elevations and color palette.

REVIEWER: DCE 791-4505 DATE: 04/22/04
Department of Urban Planning and Design
Highlands Free School
Review Comments D04-0011


Condition #2 of the Zoning Examiner’s report states that dimensioned building elevations and color palette shall be submitted at development review to ensure compatibility with existing on-site buildings. Please provide elevations that will show these requirements.

2. Condition #3 of the Zoning Examiner’s report states that side and rear building façades shall be designed with attention to architectural character compatible with the front façade. Design treatment shall include comparable color palette, lighting, screening, signage, rooflines and materials. Please show these requirements on the appropriate sheets.

3 Condition #5 of the Zoning Examiner’s report states that freestanding signs shall be integrated into the overall landscape plan and identified on the landscape and development plans. A sign detail shall be submitted as part of the development. Please show these requirements on the appropriate sheets, and submit a sign detail as requested.
04/23/2004 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this DP:

1. Show the SVT's coming from the new parking area onto 15th street.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
04/26/2004 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Highlands Free School
REVIEWER: Doug Williams
DATE: 26 April 2004
ACTIVITY NUMBER: D04-0010

Resubmittal Required: Revised Development Plan and Landscape Plan.

SUMMARY: Engineering Division has reviewed the subject Development Plan, Landscape Plan and Drainage Report. Approvals of the Development and Landscape plans are not recommended at this time. The drainage report is approved for Development Plan purposes. Please provide a response letter to the comments provided below and address all comments on revised Development and Landscape Plans.

DEVELOPMENT PLAN:
1. Depict and identify the Arroyo Chico Watercourse on the project-location map, in accordance with Development Standard (DS) 2-05.2.1 D2.
2. Please ensure all easements are clearly depicted and labeled, with recording information provided on the plan - see additional requirements outlined for these Development Standards (DS 2-05.2.3 B & D, 2-05.2.4 G).
3. Correct the City Field Book number referenced, and provide confirmation of the basis of elevation's existence. The reversible lanes have been eliminated on Broadway Blvd., and the corresponding signals and bases may no longer be in place (DS 2-05.2.3 E).
4. Please ensure all dimensioning from street monument lines to curb, sidewalk, and all utility locations is provided, fully labeled (DS 2-05.2.4 D 2).
5. Show all right of way dedications on or abutting the site and label accordingly. Specifically, indicate whether the alley identified still exists as a public alley. If so, revise the plan accordingly, if vacated, provide recording information on the plan (DS 2-05.2.4 E).
6. Identify all existing sidewalks along Highland Ave. and 15th Street rights of way (DS 2-05.2.4 L).
7. Omit or revise keynote #'s 16 and 25 (on sheet 2) at the proposed driveway entrance, and provide a note for construction of a new driveway apron, as indicated on sheet 3, in accordance with City of Tucson/ Pima County Standard Detail 206 (2003 Edition), at this location.
8. Depict and label sight visibility triangles at 15th street ingress/egress (DS 2-05.2.4 R).
9. Depict a centralized onsite refuse provision, vehicle maneuverability and access for the proposed dumpster(s), and provide a typical enclosure detail, fully dimensioned and labeled (DS 2-05.2.4 T). Onsite refuse provision development standards, including dumpster placement, access to and from, enclosure and bin requirements, etc., can be found in DS 6-01.0.
10. Address roof drainage direction(s) and depict and label roof downspout locations and associated sidewalk scuppers for conveyance of the 10-year rainfall event at a minimum, under sidewalk areas (DS 2-08.4.1 E and 3-01.4.4 F).
11. Remove General Note # 13 (Sheet 1). Prior to any grading activity, a grading permit application and approved grading plans may be required for this development.
12. Please address the existing alley identified on the western perimeter of the site, and provide any vacation, abandonment, or purchase information, with recording information on the plan. If the alley is still public, the plan must be revised to omit incorporation of this area on the site. See any additional Zoning Review comments relating to this matter.
GENERAL COMMENTS:
1. The consultant may wish to omit Streets and Roads Note number 1, as no new roads are proposed under this site development.
2. Omit General Grading Notes 13 and 14 on sheet 3.

LANDSCAPE PLAN:
1. Demonstrate water harvesting in landscape areas to the maximum extent reasonably possible, per Land Use Code, Section 3.7.4, and SMDDFM, Sec. 14.2.10.
2. The 10' TEP easement identified on the western perimeter appears as an alley on the Development Plan. Please revise and ensure consistency between the two plans prior to resubmittal.

Resubmittal shall require revised Development and Landscape Plans.

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
04/26/2004 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the landscape plan to propose 2:1 mitigation for any protected plants removed. Note the quantity of mitigation plants of the same species on the plan.

2) Submit a copy of the plan referred to in the conditions for DRB Case # 03-11, the plan reviewed at the June 13, 2003 meeting
04/27/2004 DAN CASTRO ZONING REVIEW Denied COMMENTS
CODE SECTION/ DEVELOPMENT STANDARD

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is March 25, 2005.

2. List the name, address, and telephone number of the developer.
D.S. 2-05.2.2.A.1

3. This project has been assigned development plan case number D04-0010. Please note the case number in the lower right corner of each sheet on all plans.
D.S. 2-02.2.2.B.2

4. a) Under general note two (2), please note the grade levels taught.
b) Correct the spelling "purposed" under general note two (2).
D.S. 2-05.2.2.B.3

5. If applicable, all existing and proposed easements on this site must be shown on the plan, including the type, width, recordation information, and whether they will be private or public.
D.S. 2-05.2.3.B/ D.S. 2-05.2.4.G

6. Keynote 15 indicates driveway width is 24 feet. The driveway entrance does not measure 24 feet when scaled. Please verify that 24 feet is in fact provided.
D.S. 2-05.2.4.D.3

7. If portion of alley has been vacated please state as so on plan and provide docket and page reference (recording information).
D.S. 2-05.2.4.E

8. The five (5) foot wide sidewalk located west of the proposed building must be physically separated from the vehicular use area by means of curbing, grade separation, barriers, railings, or other means.
D.S. 2-05.2.4.K/ D.S. 2-08.4.1

9. The square footage for the existing building listed under general note five (5) 2,251 Sq. Ft. does not match the square footage listed on sheet 2 of 3 (3,834 Sq. Ft.). Revise for accuracy.
D.S. 2-05.2.4.M

10. a) Provide the lot coverage calculation.
b) Floor area ratio calculation may not be verified for compliance until the correct existing building area has been listed on the plan (comment 12).
D.S. 2-05.2.4.M

11. a) Dimension the vehicle overhang area. Maximum overhang area allowed is 2.5 feet. Revise length of vehicle parking spaces to 15.5 feet.
b) Label and dimension the existing drop-off parking spaces. One (1) of the four drop off spaces must be accessible.
D.S. 2-05.2.4.P/ D.S. 3-05.2.3.C.2

12. a) One (1) van accessible parking space with an eight (8) foot wide access aisle is required on-site. Per IBC Section 1106.5, accessible parking spaces shall be located on the shortest accessible route of travel from adjacent parking to an accessible building entrance.
b) Detail disabled parking, access aisle, and access ramp. Post disabled parking sign.
D.S. 2-05.2.4.P/ 2000 IBC 1106.5

13. a) Provide a fully dimensioned Class II bicycle parking space detail. Refer to D.S. 2-09 for design criteria.
b) Under the bicycle parking calculation on sheet 1 of 3, list the class type required and provided (Class II).
D.S. 2-05.2.4.Q/ D.S. 2-09

14. a) Provide a sign detail. Special Exception condition number five (5).
b) Where is the existing sign (Keynote 19) ?

15. Keynote 23 indicates a sandbox, which is located in the vehicle overhang area. Please relocate the sandbox.

16. All requested changes must be made to the development and landscape plans.
D.S. 2-07.2.1.A

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
04/28/2004 CRAIG GROSS OTHER AGENCIES PIMA ASSN OF GOVTS Approved
04/28/2004 JIM STOYANOFF COT NON-DSD REAL ESTATE Denied D04-0010, Highland Free School, Docket 12195, at Page 1654 vacated an alley that was to the east of this school. The City reserved an ingress/egress easement to the owner of Block 14 Lot 3 over that portion of alley vacated to Highland Free School. It appears that the chain link fence will obstruct this easement !