Permit Review Detail
Review Status: Completed
Review Details: DEVELOPMENT PLAN
Permit Number - D03-0040
Review Name: DEVELOPMENT PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2003 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 10/14/2003 | JIM EGAN | COT NON-DSD | FIRE | Approved | DATE: November 5, 2003 TO: Ferne Rodriguez, Development Services FROM: Glenn Hicks, Parks and Recreation SUBJECT: CDRC Transmittal, Project D03-0040 Tucson Federal Credit Union: DP CC: Craig Gross, Development Services Staff has no comments. Please feel free to call me at 791-4873 x 215 if you have any questions. |
| 10/14/2003 | JIM EGAN | COT NON-DSD | FIRE | Approved | The Development Plan is approved 10/14/03. |
| 10/17/2003 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | NO COMMENT D03-0040 ESQUEMA ARCHITECTURE TUCSON FEDERAL CREDIT UNION |
| 10/22/2003 | TIM ROWE | PIMA COUNTY | WASTEWATER | Needs Review | |
| 10/22/2003 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approved | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: D03-0040 TUCSON FEDERAL CREDIT UNION/DEVELOPMENT PLAN DATE: October 21, 2003 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project. NOTE: 1. Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses. 2. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection. jg |
| 10/24/2003 | ROGER HOWLETT | COT NON-DSD | COMMUNITY PLANNING | Approved | DATE: November 5, 2003 TO: Ferne Rodriguez, Development Services FROM: Glenn Hicks, Parks and Recreation SUBJECT: CDRC Transmittal, Project D03-0040 Tucson Federal Credit Union: DP CC: Craig Gross, Development Services Staff has no comments. Please feel free to call me at 791-4873 x 215 if you have any questions. |
| 10/24/2003 | ROGER HOWLETT | COT NON-DSD | COMMUNITY PLANNING | Approved | COMPREHENSIVE PLANNING TASK FORCE COMMENTS Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT D03-0040 Tucson Federal Credit Union 10/23/03 ( ) Tentative Plat () Development Plan () Landscape Plan ( ) Revised Plan/Plat ( ) Board of Adjustment () Other (NPPO) CROSS REFERENCE: C9-78-38 NEIGHBORHOOD PLAN: Santa Cruz Area Plan GATEWAY/SCENIC ROUTE: Mission Road (scenic), Ajo Way (gateway) COMMENTS DUE BY: November 10, 2003 SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: ( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment () Proposal Complies with Annexation or Rezoning Conditions ( ) RCP Proposal Complies With Plan Policies ( ) See Additional Comments Attached ( ) No Additional Comments - Complies With Planning Comments Submitted on: ( ) Resubmittal Required: ( ) Tentative Plat ( ) Development Plan ( ) Landscape Plan ( ) Other REVIEWER: K. Aragonez 791-4505 DATE: October 20, 2003 |
| 11/05/2003 | GLYNDA ROTHWELL | UTILITIES | TUCSON ELECTRIC POWER | Denied | SUBJECT: TUCSON FEDERAL CREDIT UNION D03-0040 Tucson Electric Power Company (TEP) has reviewed the plans dated October 8, 2003. TEP is unable to approve the plans at this time. There are existing electrical facilities within the boundaries of this project. In order for TEP to approve the plans, the facilities and easement recording information must be depicted on the plans. Enclosed is a copy of a TEP facility map and the development plan showing the approximate location of the existing facilities. The underground facilities may be located under the addition once development is complete. All cost associated with the relocation of the facilities in conflict will be billable to the developer. Please resubmit two revised bluelines to the City of Tucson for TEP's review. Liza Castillo Land Management Tucson Electric Power Company lcastillo@tucsonelectric.com (520) 884-3882 |
| 11/05/2003 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | DATE: November 5, 2003 TO: Ferne Rodriguez, Development Services FROM: Glenn Hicks, Parks and Recreation SUBJECT: CDRC Transmittal, Project D03-0040 Tucson Federal Credit Union: DP CC: Craig Gross, Development Services Staff has no comments. Please feel free to call me at 791-4873 x 215 if you have any questions. |
| 11/12/2003 | DALE KELCH | COT NON-DSD | TRAFFIC | Approved | DATE: November 5, 2003 TO: Ferne Rodriguez, Development Services FROM: Glenn Hicks, Parks and Recreation SUBJECT: CDRC Transmittal, Project D03-0040 Tucson Federal Credit Union: DP CC: Craig Gross, Development Services Staff has no comments. Please feel free to call me at 791-4873 x 215 if you have any questions. |
| 11/12/2003 | DALE KELCH | COT NON-DSD | TRAFFIC | Approved | Traffic Engineering recommends APPROVAL of this DP D. Dale Kelch, EIT Senior Engineering Associate Traffic Engineering Division (520)791-4259x305 (520)791-5526 (fax) dkelch1@ci.tucson.az.us |
| 11/13/2003 | JOE LINVILLE | LANDSCAPE | REVIEW | Denied | 1) Revise sheet 1 of the development plan to exclude the new canopy tree information from the legend if it is inaccurate. 2) Provide verification, in writing, of approvals obtained for use of the public right of way for landscaping from the City Engineer. LUC 3.7.2.9.A 3) Provide clarification regarding the location of the 1' no access easement shown on the plans at the drive from Mission Road. |
| 11/13/2003 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | To: Craig Gross DATE: November 13, 2003 Planning Administrator FROM: Loren Makus Engineering Division SUBJECT: 3755 S Mission Road. Development Plan D03-0040 Tucson Federal Credit Union (First Review) T14S, R13E, Section 227 RESUBMITTAL NOT REQUIRED. The Development Plan has been reviewed. At this time the Engineering Division recommends approval of the Development Plan for Tucson Federal Credit Union. If you have any questions, I can be reached at 791-5550 x1161 or lmakus1@ci.tucson.az.us Loren Makus Senior Engineering Associate C:/ 3755 S. Mission Road |
| 11/18/2003 | DAVID RIVERA | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera Senior Planner FOR: Patricia Gehlen Principal Planner PROJECT: D03-0040 Tucson Federal Credit Union Financial Services Use - DD "34" Development Plan TRANSMITTAL: November 18, 2003 DUE DATE: November 10, 2003 COMMENTS: 1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is October 13, 2004. 2. List in the lower right corner next to the title block the development plan case number which was assigned to this project D03-0040. The case number must be listed on all development plan sheets including the landscape sheets. DS 2-05.2.2.B.5 3. Revise note "B" under the Development Plan Notes text block to include the 'allowed use and subject to condition section' as listed in the Land Use Code. The use should be listed as Financial Service DD "31" Subject to LUC section 3.5.13.5. Revise as required. DS 2-05.2.2.B.3 4. Add a general note that states that this project has been designed to meet the criteria of the Gateway Route Overlay Zone LUC 2.8.4 and Major Streets and Routes Setback Zone LUC 2.8.3. DS 2-05.2.2.B.10 5. If applicable, all existing or proposed easements must be drawn on the plan. The location, purpose, width, and recordation information must be listed. DS 2-05.2.3.B and DS 2-05.2.4.G 6. Revise the zoning classification adjacent to the east property line, which is listed as C-2 to C-1. DS 2-05.2.4.B 7. Label the future building setback from the back of future curb location. The building setback is based on the greatest of 21 feet or the height of the structure. This site is within 700 feet from the intersection of Ajo Way and Mission Road and is not subject to the Scenic Corridor criteria. The project is subject to the criteria of the Gateway Route LUC section 2.8.4. DS 2-05.2.4.I 8. List as a note or label on the building footprint the existing and proposed building heights. DS 2-05.2.4.N 9. List under the parking calculations, the number of required and number of loading zones provided. DS 2-05.2.4.O 10. This is obviously a shopping center with a gross floor area of greater than 50,000 square feet. Therefore the parking ratio for this shopping center is one space per 200 square feet of the total gross floor area of the buildings in this center. This ratio may be used as long as the gross floor area of the buildings is greater than 50 percent retail/office area. Please list the uses currently occupying all available suites in this center. The list should include the name of the business, the use as classified by the land use code, and the square footage. This will be the latest development plan/site plan, which will be the most current for the center and should include the requested information. Please revise the parking calculations to indicate the existing conditions and shopping center parking ratio. List the number of vehicle-parking spaces required and the number of provided. Please call me if you have any questions regarding this comment. DS 2-05.2.4.P 11. The bicycle parking requirements for a shopping center of greater than 50,000 square feet is based on eight (8) percent of the total number of vehicle parking spaces provided. Of the required bicycle parking spaces 50 percent must be class one and fifty percent must be class two. Please indicate or list the locations and type of facilities provided. Please indicate or list the locations and type of facilities provided. DS 2-05.2.4.O 12. Indicate the location and type of postal service to be provided. DS 2-05.2.4.V 13. Indicate the location, type and size of existing or proposed signage for the proposed use. DS 2-05.2.4.W 14. See the comments by the landscape reviewer regarding the requirements for the landscape borders, screening, and NPPO. DS 2-05.2.4.X 15. Please clarify the last note under the Development Plan Parking Calculation that refers to the existing 32 parking spaces used for bike and tree planting. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. DGR C:\planning\cdrc\developmentplan\D030040dp.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and landscape plans and additional requested documents |
| 11/20/2003 | CRAIG GROSS | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | |
| 11/20/2003 | JIM STOYANOFF | COT NON-DSD | REAL ESTATE | Approved | DATE: November 5, 2003 TO: Ferne Rodriguez, Development Services FROM: Glenn Hicks, Parks and Recreation SUBJECT: CDRC Transmittal, Project D03-0040 Tucson Federal Credit Union: DP CC: Craig Gross, Development Services Staff has no comments. Please feel free to call me at 791-4873 x 215 if you have any questions. |