Permit Number: D03-0032
Parcel: 11105063J

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D03-0032
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2003 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/25/2003 JIM EGAN COT NON-DSD FIRE Approved The Development Plan is approved 8/25/03.
08/25/2003 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: August 25, 2003

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, Project D03-0032 AGM Container Controls Inc: Development Plan

CC: Craig Gross, Development Services


Staff has no comments.

Please feel free to call me at 791-4873 x 215 if you have any questions.
08/28/2003 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
D03-0032
STEVEN C. SHELL. ARCHITECT
AGM CONTAINER CONTROLS, INC.
08/28/2003 TIM ROWE PIMA COUNTY WASTEWATER Needs Review
08/28/2003 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D03-0032 AGM CONTAINER CONTROLS, INC / DEVELOPMENT PLAN
DATE: August 28, 2003



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1: Development Plan needs to include Legal Description. Legal Description should
include Lots, Block, Subdivision and Book and Page.

2: Correct Palo Verde Ave. to Palo Verde Avenue.

3: Correct Ft. Lowell Road to Fort Lowell Road.

4: Revise Location Map per CDRC requirements.
09/03/2003 BLANCA ESPINO ENGINEERING REVIEW Approv-Cond Indicate Cut/Fill qty. on Dev. Plan. If Fill qty. is over 50 c.y., a Grading Permit will be required.
09/04/2003 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved Tucson Electric Power Company has reviewed and approved the development plan dated August 8, 2003.  It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.  If a conflict does exist , the relocation costs will be billable to the developer.

Please submit a final set of plans including electrical load plans, to determine how TEP will serve this commercial development. Plans must be submitted to TEP a minimum of six weeks prior to requiring service.  If easements are required, they will be secured by separate instrument. 

Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tucsonelectric.com
(520) 884-3882
09/08/2003 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Case Number: D03-0032
Project Name: AGM Container Controls, Inc.
Estimated Traffic Generation: 62 trips
09/18/2003 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL


TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner


PROJECT: D03-032
AGM Container Controls, Inc.
Development Plan

TRANSMITTAL: September 18, 2003
DUE DATE: September 18, 2003


1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for full CDRC review. The one year expiration date for this development plan is August 20, 2004.

2. Place the development plan number (D03-032) on each sheet of the development plan, landscape plan and NPPO plans in the lower right hand corner near the title block.
DS 2-05.2.2.B.2

3. List all conditions for rezoning case number C9-85-79 on the revised development plan.
DS 2-05.2.2.B.2

4. Provide the development designator for the proposed use in the P-I zone. The development designator for the general manufacturing use is use in the P-I zone is "33". Also, the manufacturing use is subject to LUC 3.5.5.1.B, .D, .E, .F, and .H. Please add a note detailing these restrictions. LUC 2.7.1.2.A.2

5. If any new freestanding lighting or signage is proposed as part of this expansion, indicate location and type.
DS 2-05.2.4.N

6. Add the docket and page for the recordation of the cross access/cross parking agreement with the property to the east.

7. Add the proposed building height to the plan. DS 2-05.2.4.N

8. Provide a Floor Area Ratio (FAR) calculation on the development plan, including both the maximum allowed and the proposed FAR. LUC 3.2.3.2.B

9. For uses providing from 76 to 100 total parking spaces, 4 handicapped accessible spaces are required. Please revise h/c parking spaces to indicate that while 5 h/c spaces are provided, only 4 are required. ANS/IBC

10. Dimension the depth of the two backup spurs (the one at the south end of the southwest parking lot and the other one at the north end of the southeast parking lot.
DS 3-05.2.2.D

11. If easements exist or are proposed on the property, show their location, width, type, and provide recordation info.
DS 2-05.2.3.B

12. Dimension the width of the entrance drive from Ft. Lowell Road. DS 2-05.2.4.D

13. Provide a brief legal description of the property. DS 2-05.2.1.G.2

14. Fort Lowell Road is a designated MS&R. Add a note stating that the plan is designed to meet the criteria of LUC 2.8.3, Major Streets and Routes Setback Zone DS 2-05.2.2.A.10

15. Revise bicycle parking to also indicate the number of class 1 and class 2 spaces provided. Revise calculation of required bicycle parking to be based on 8% of the number of vehicle parking spaces provided, which is 96. Note: This will not change the total required number of bicycle spaces (8). DS 2-05.2.4.Q

16. All requested changes must be made to the Development Plan and Landscape Plan. DS 2-07.2.1.A


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan.

























PSMc\H\devplans03\D03-020rev1.doc
09/18/2003 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D03-0032 AGM Container Controls, Inc. 9/17/2003

( ) Tentative Plat
(ü) Development Plan
(ü) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
(ü) Other (PDO-02-04)

CROSS REFERENCE: C9-85-79, C9-77-32, C10-86-92

NEIGHBORHOOD PLAN: Grant Alvernon Area Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: September 18, 2003

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
(ü) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
(ü) Resubmittal Required:
( ) Tentative Plat
(ü) Development Plan
(ü) Landscape Plan
(ü) Other (Photos of Surrounding Area)

REVIEWER: K. Aragonez 791-4505 DATE: September 8, 2003


AGM Container Controls, Inc. D03-0032


1) Please place all rezoning conditions on the development plan. This will provide verification that conditions concerning lighting, times of operation, etc. are acknowledged and will be enforced.

2) Rezoning condition 1b requires access onto Palo Verde Avenue limit traffic to exit right only. The curbing as shown on the plan may not deter people from making a right turn into the neighborhood. Placement of a "No Left Turn" or "Right Turn Only" sign would reinforce this requirement. If one already exists please indicate its location on the development plan.

3) Rezoning condition 7 requires that proposed colors and materials are submitted as part of the development plan and that color photographs of the surrounding properties shall accompany the submittal. Please indicate color palette on the plan elevation of the proposed addition. Provide color photographs of surrounding properties to demonstrate compatibility of new addition to the neighborhood.

4) Per rezoning condition 12, roof mounted exterior equipment must be located to minimize visibility from adjacent residential development and street frontages, and all ground mounted equipment must be fully screened. Identify the location of all mechanical equipment. Indicate by detail or note how screening and/or location meet this condition.

5) It is unclear if the new wall along the south property line is incorporating graffiti-resistant materials and a decorative material as required by rezoning condition 16. Please indicate by note how wall complies with this condition of rezoning.

6) Please clarify the location of new landscaping shown along the new south wall adjacent to the R-2 zoning. It does not appear that shrubs are being placed within notches exposed to the R-2 property. Please indicate by detail or note that notches are being planted with proposed shrubs.
09/18/2003 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL


TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner


PROJECT: D03-032
AGM Container Controls, Inc.
Development Plan

TRANSMITTAL: September 18, 2003
DUE DATE: September 18, 2003

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for full CDRC review. The one year expiration date for this development plan is August 20, 2004.

2. Place the development plan number (D03-032) on each sheet of the development plan, landscape plan and NPPO plans in the lower right hand corner near the title block.
DS 2-05.2.2.B.2

3. List all conditions for rezoning case number C9-85-79 on the revised development plan.
DS 2-05.2.2.B.2

4. Provide the development designator for the proposed use in the P-I zone. The development designator for the general manufacturing use is use in the P-I zone is "33". Also, the manufacturing use is subject to LUC 3.5.5.1.B, .D, .E, .F, and .H. Please add a note detailing these restrictions. LUC 2.7.1.2.A.2

5. If any new freestanding lighting or signage is proposed as part of this expansion, indicate location and type.
DS 2-05.2.4.N

6. Add the docket and page for the recordation of the cross access/cross parking agreement with the property to the east.

7. Add the proposed building height to the plan. DS 2-05.2.4.N

8. Provide a Floor Area Ratio (FAR) calculation on the development plan, including both the maximum allowed and the proposed FAR. LUC 3.2.3.2.B

9. For uses providing from 76 to 100 total parking spaces, 4 handicapped accessible spaces are required. Please revise h/c parking spaces to indicate that while 5 h/c spaces are provided, only 4 are required. ANS/IBC

10. Dimension the depth of the two backup spurs (the one at the south end of the southwest parking lot and the other one at the north end of the southeast parking lot.
DS 3-05.2.2.D

11. If easements exist or are proposed on the property, show their location, width, type, and provide recordation info.
DS 2-05.2.3.B

12. Dimension the width of the entrance drive from Ft. Lowell Road. DS 2-05.2.4.D

13. Provide a brief legal description of the property. DS 2-05.2.1.G.2

14. Fort Lowell Road is a designated MS&R. Add a note stating that the plan is designed to meet the criteria of LUC 2.8.3, Major Streets and Routes Setback Zone DS 2-05.2.2.A.10

15. Revise bicycle parking to also indicate the number of class 1 and class 2 spaces provided. Revise calculation of required bicycle parking to be based on 8% of the number of vehicle parking spaces provided, which is 96. Note: This will not change the total required number of bicycle spaces (8). DS 2-05.2.4.Q

16. All requested changes must be made to the Development Plan and Landscape Plan. DS 2-07.2.1.A


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan.
09/18/2003 JIM STOYANOFF COT NON-DSD REAL ESTATE Approved No comment
09/24/2003 DALE KELCH COT NON-DSD TRAFFIC Approved no comments.
09/25/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Clarify on the Development Plan that mechanical equipment will be screened entirely from the street in accordance with LUC Table 3.7.2-I. Revise the notes related to roof top HVAC equipment as necessary.

2) PDO 02-04 expired 180 days from November 27, 2002. Contact Zoning Administration regarding the possibility of a time extension.

3) Landscape buffers are to be a minimum of 10' wide per LUC 3.7.2.4.

4) A six-foot high masonry wall and landscaping is required along the south property line of Lot 5 per C9-85-79.

5) Show sight visibility triangles on the landscape plan and revise the plans to locate elements which obscure visibility
between thirty and seventy two inches. Plants which typically exceed thirty inches in height should not be located in SVT's.
LUC 3.7.2.8