Permit Number: D03-0020
Parcel: 13325186H

Review Status: Completed

Review Details: RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D03-0020
Review Name: RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2003 FRODRIG2 START PLANS SUBMITTED Completed
08/26/2003 JIM EGAN COT NON-DSD FIRE Denied An approved turnaround is required for dead-end P.A.A.L. minimum fire access roadway width is 20 feet including all portions of the turnaround. Loading zone cannot be located in turnaround area.
09/03/2003 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL


TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
D03-020
Huntington Park Plaza
Development Plan
3rd review

TRANSMITTAL: September 3, 2003
DUE DATE: September 8, 2003


1. Place the development plan number (D03-020) on all sheets, including the landscape plan and the irrigation plan, in the lower right hand corner near the title block.

2. Revise zoning setback table to specify that the MS&R setback from Speedway Blvd. is the greater of 21 feet or the height of exterior structure wall measured from back of future curb.
LUC 3.2.6.5

3. Provide a copy of recorded cross access/ cross parking agreement and add the recordation information (docket and page numbers) for the agreement to the development plan notes.
DS 2-05.2.4.N

4. Bicycle parking calculation shows that 4 class 2 spaces are proposed but a revised total of 6 (2 for each building) are now shown on the. Please revise bicyle parking calcs. Add a statement to the calcs that two bicycle parking spaces are provided for each building,
DS 2-09.4.1

5. It is acknowledged that a Board of Adjustment Variance application will be submitted to seek relief from the loading zone requirement. Once, the variance is approved, add the variance case number, date of approval, what was approved and conditions to the general notes.
LUC 3.4.4.1.B.2

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan, cross access/cross parking document.
09/11/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The site must be screened from the residentially zoned property to the south. LUC 3.7.3
( The addition of one-gallon shrubs is not sufficient to meet this requirement, a 5' wall is required.)

2) Screening per LUC Table 3.7.2-I is required along the west property line to screen the parking area from the adjacent O-3 zoned property north of building 'A' (where no screen currently exists).
( A 5' high wall will be required.)

3) The loading area must be screened from the adjacent O-3 property and from the adjacent R-1 property with a six foot high masonry wall per LUC Table 3.7.2-I.
(Note the height of any existing walls and revise the plans to include new walls where necessary to meet the minimum requirements.)

Resubmittal of the Development/Landscape Plan is required.
Provide a response letter with the resubmittal.