Permit Number: D03-0020
Parcel: 13325186H

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D03-0020
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2003 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/02/2003 JIM EGAN COT NON-DSD FIRE Denied 1. Provide a General Note on the plan stating:"Additional fire hydrants shall be provided by the developer in accordance with the Fire Code".
2. An approved turnaround shall be provided for dead-end PAAL.
05/08/2003 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D03-0020 HUNTINGTON PARK PLAZA / DEVELOPMENT PLAN
DATE: May 5, 2003



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:


1: Label suffix for all street names in Location Plan.

2: Title Block should include: Portion of Lot 177 of Huntington Park, Bk 15, Pg. 48.

3: Correct building letters to building numbers.

4: Correct Bella Vista Homeowners, Inc. to Bella Vista Townhomes on Sheet 2.
05/19/2003 LOREN MAKUS ENGINEERING REVIEW Denied RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage statement cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:
1. Please include a response letter to the comments along with the corrected copies with re-submittal.
2. Show future curb and sidewalk locations. D.S. 2-05.2.4. F
3. Label and dimension future sight visibility triangles per D.S. 2-05.2.4.D.3
4. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-05.2.4.K
5. Fully-dimensioned loading space(s) and maneuvering area(s) per D.S. 2-05.2.4.O.
6. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-05.2.4.F.
7. Show Development plan number on all sheets per D.S. 2-05.2.2.B.2.
8. Show refuse container access fully dimensioned per D.S. 2-05.2.4.T and D.S. 6-01.0.
9. A right-of-way permit will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information
10. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.







Drainage Statement:

11. The Drainage Statement which is an amendment to a previously submitted Drainage Report cannot be accepted without the original Drainage Report. Please submit the complete Drainage Report along with the amendment.
D.S. 2-05.3.1.E.
12. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

If you have any questions, I can be reached at 791-5550 x1161 or lmakus1@ci.tucson.az.us.
Loren Makus
Senior Engineering Associate
C:/ 8480 E Speedway Blvd.
05/22/2003 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Case Number: D03-0020
Project Name: Huntington Park Plaza
Estimated Traffic Generation: 81 trips

If you have any questions or need more information, please contact me.

Sandy White
Research & Statistical Analyst
Pima Association of Governments
ph: 520-792-1093 x108
fax: 520-792-9151
swhite@pagnet.org
05/28/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) A more detailed landscape plan is required at the time of application for permits. For more specific information, refer to Development Standard 2-07.0. The NPPO application for exception has been accepted and approved.

2) Screening per LUC Table 3.7.2-I is required along the west property line to screen the parking area from the adjacent O-3 zoned property north of building 'A'. Note the height of the existing wall on the adjacent property along the west property line. DS 2-07.2.2.A.3

3) The loading area must be screened form the adjacent O-3 property with a six foot high masonry wall per LUC Table 3.7.2-I.

4) The refuse storage area must be screened per LUC Table 3.7.2-I.

5) A seperate NPPO plan may be required for any disturbance of the public right-of-way vegetation. Contact Gary Wittwer for additional information at the Tucson Department Of Transportation 791-5100.
05/29/2003 PETER MCLAUGHLIN ZONING REVIEW Denied TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner


PROJECT:
D03-020
Huntington Park Plaza
Development Plan

TRANSMITTAL: May 29, 2003
DUE DATE: May 27, 2003


1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for full CDRC review. The one year expiration date for this development plan is April 29, 2004.

2. Place the development plan number (D03-020) on each sheet of the development plan, landscape plan and NPPO plans in the lower right hand corner near the title block.
DS 2-05.2.2.B.2

3. Label future curb location and future sight visibility triangles, if different from existing curb location, and dimension curbs from street monument lines.
DS 2-05.2.4.F & R

4. Continuous pedestrian circulation must be provided between all of the buildings and the sidewalk along the Speedway Blvd frontage.
DS 2-08.5.1
DS 2-05.2.4.K

5. If any new freestanding lighting or signage is proposed as part of this development, indicate location and type.
DS 2-05.2.4.N

6. MS&R bldg setback is required to be the greater of 21' or height of structure wall measured from back of future curb. Revise zoning setback data table and keynote #16 as this 10 foot dimension is a landscape border area.
LUC 3.2.6.5

7. The required setback to the west property line (adjacent property zoned 0-3) is 0 feet. Please revise. LUC 3.2.6.4

8. Provide a Floor Area Ratio (FAR) calculation on the development plan. The FAR is calculated as the gross floor area divided by the lot area. The lot coverage calculation may be removed as it is not necessary or required for nonresidential development designators in nonresidential zones. LUC 3.2.3.2.B

9. Per IBC Sec. 1106.4, one handicapped parking space must be van accessible, and be provided with an access aisle with a minimum width of 8 feet. Please revise drawing, which shows no van accessible parking provided for the project. ANS/IBC

10. Dimension the depth of the backup spur and the distance between the backup spur and the existing fence along the east property line. A minimum 3-foot deep backup spur is required and a minimum of 3 feet is required between the end of the spur and the fence to allow for vehicle overhang.
DS 3-05.2.2.D

11. If easements exist or are proposed on the property, show their location, width, type, and provide recordation info.
DS 2-05.2.3.B
12. Dimension the width of the entrance drive. DS 2-05.2.4.D.3

13. On projects containing more than one building, loading zones must be provided for each building. Please revise development plan and loading space calcs. Also, it appears that there is not adequate maneuverability for trucks to maneuver back out of the loading zone. Please revise. LUC 3.4.4.1.B.2

14. The legal description in the title block is incorrect. Please revise legal description to be correct DS 2-05.2.1.G.2

15. Revise required bicycle parking to read 8% of vehicle parking spaces provided, and remove the reference to "4 or more units" as this is not a residential development. DS 2-05.2.4.Q

16. A minimum distance of 2 feet must be maintained between a PAAL and any wall, screen or other obstruction provided pedestrian activity is directed to another location. Dimension the distance between the edge of the PAAL and the CMU wall along the west property line. DS 3-05.2.2.B.3

17. A wheelstop must also be provided in the h/c parking space adjacent to building A. DS 3-05.2.3.C


18. All requested changes must be made to the Development Plan and Landscape Plan. DS 2-07.2.1.A


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan.
05/30/2003 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: May 28, 2003

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, Project D03-0020 Huntington Park Plaza, Development Plan

CC: Craig Gross, Development Services


Staff has reviewed and has no comments.

Please feel free to call me at 791-4873 x 215 if you have any questions.
05/30/2003 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D03-0020 Huntington Park Plaza 05/28/03

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Pantano East Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: 5/27/03

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(X) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: msp 791-4505 DATE: 5/27/03
05/30/2003 FRODRIG2 COT NON-DSD REAL ESTATE Approved
06/02/2003 TIM ROWE PIMA COUNTY WASTEWATER Approv-Cond PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
June 17, 2003

TO: Mark Hanshaw, Arcadis G & M

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Huntington Park Plaza
Development Plan - 1st Submittal
D03-0020



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Per Pima County Wastewater Management’s Planning Services, there is currently capacity in the existing downstream sewerage system for this development. This response is not to be construed as a commitment for conveyance capacity allocation, but rather an analysis of the existing sewerage system as of this date.

2. Based on the preliminary sewer layout as shown on the referenced development plan, this project would qualify for Non-Participating sewer connection fee rates. However, a final determination of this status cannot be made until approval of the sewer construction plans and/or preparation of the sewer service agreement.

3. The development plan is hereby approved, subject to the following:

4. Add the development plan case number, D03-0020, to the title block of each sheet. This number should be shown larger or bolder than the cross reference numbers.

5. Sheet 1: Delete the quotation marks from General Notes 12 & 13.

6. Sheet 2: Revise the finish floor elevations for Buildings B & C to read either 01.0 or 601.0.

If you wish to discuss the above comments, please contact me at 740-6563.



Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

TR/tr
Copy: Project
06/02/2003 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this DP

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dkelch1@ci.tucson.az.us
06/02/2003 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Denied 3950 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


Telephone: 520-884-3879
Fax: 520-770-2002
WR#106665 June 11, 2003



Mr. Mark Hanshaw
Arcadis G&M
285 W. 18th Street
Tucson, Arizona 85701

Dear Mr. Hanshaw:

SUBJECT: Huntington Park Plaza
D03-0020

Tucson Electric Power Company (TEP) has reviewed the plans dated April, 2003. TEP is unable to approve the plans at this time. There are existing underground electric cable within the area shown as the off-site improvements area north of the property. These facilities need to be identified by blue stake and pot holed, and shown on a revised Development Plan in the correct location.

Enclosed is a copy of a TEP facility map and the Development Plan showing the approximate location of the existing facilities. Any costs associated with the relocation of the facilities in conflict shall be billable to the developer.

Please resubmit two revised bluelines to the City of Tucson for TEP's review. You may contact me at (520) 884-3879 if you have any questions.

Sincerely,



S. Glynda Mastrangelo
Right-of-Way Agent
Land Management

sgm
Enclosure
cc: C. Gross, City of Tucson
06/02/2003 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Passed