Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D03-0006
Parcel: 10309074H

Review Status: Completed

Review Details: RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D03-0006
Review Name: RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2003 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/21/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Southwest Ambulance Facility
REVIEWER: Doug Williams
DATE: 21 March 2003
ACTIVITY NUMBER: D03-0006

Resubmittal Required: Development Plan/Landscape Plan

SUMMARY: Engineering Division has reviewed the Development Plan, Landscape Plan and Drainage Report received on April 11, 2003. The Drainage Report is acceptable for Development Plan approval purposes. Revised Development and Landscape Plans may be approved upon addressing the following items:

DEVELOPMENT PLAN:

1. Provide a General (drainage) Note that, "This project is affected by the City of Tucson Floodplain Regulations", as determined in the drainage report (DS 2-05.2.2 C 2 a);
2. Correct the west basin bottom elevation to 2265.1;
3. Correct the retention basin callout directions to face south, so that the cross sections provided are accurate.

LANDSCAPE PLAN:

1. Demonstrate water harvesting in landscape areas to the maximum extent reasonably possible, per Land Use Code, Section 3.7.4, and SMDDFM, Sec. 14.2.10.


Please provide a revised Development Plan and Landscape Plan.

As stated on the previous comment letter, prior to grading activity, approved grading plans, stormwater pollution prevention plans and a floodplain use permit will be required.

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
04/24/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the landscape plan to properly identify the zoning west of the project as R-1 as indicated in this submittal on the development plan. This use located adjacent to residentially zoned property must be screened with five-foot high masonry wall. LUC Table 3.7.2-I. Revise the development and landscape plans to meet the screening requirement.

2) The addition of loading areas south of the building requires revision to proposed screening. Loading areas, if located within 100 feet of and adjacent street must be screened with a six-foot high masonry wall. LUC Table 3.7.2-I
Revise the development and landscape plans to screen the loading areas from River Park Drive with a six-foot high wall.

3) The proposed screening along River Park Drive must provide a visual barrier between the different land uses, enhance the streetscape, assist in wind control and dust and noise reduction, and provide privacy. LUC 3.7.3

Provide information on how the wrought iron fence will meet these objectives, typically the type of fence proposed does not meet the minimum requirements. By definition, the screen is to provide "an opaque barrier designed and constructed to conceal areas used for storage, refuse, mechanical equipment, parking, or delivery service loading bays from street and public view or to buffer adjacent land uses." LUC 6.2.19
Revise the landscape and development plans as necessary.
04/24/2003 DAVID RIVERA ZONING REVIEW Approved TO: Plans Coordination Office
Development Services Department

PROJECT: D03-0006
Southwest Ambulance Facility
Development Plan

FROM: David Rivera
Senior Planner

FOR: Patricia Gehlen
Principal Planner
Zoning Review Section

TRANSMITTAL: April 24, 2003

DUE DATE: April 24, 2003

The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

If you have any questions about this transmittal, please call David Rivera at (520) 791-5608.

C:\planning\cdrc\developmentplan\D0300006dpa.doc
04/28/2003 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: April 28, 2003

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

RE: CDRC Transmittal, Project D03-0006 Southwest Ambulance Facility: Resubmital Development Plan


CC: Craig Gross, Development Services


Staff has reviewed and approved.