Permit Number: D03-0005
Parcel: 12218162B

Review Status: Completed

Review Details: RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D03-0005
Review Name: RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2003 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/25/2003 JIM TATE ENGINEERING REVIEW Denied TO: Craig Gross; CDRC Coordinator
DATE: July 25, 2003

SUBJECT: Engineering review of the Assistance League Expansion Development Plan. The activity number is D03-0005.

SUMMARY: The Development Plan and Drainage Report were received by Engineering on July 25, 2003. Engineering has reviewed the received items and does not recommend approval of the Development Plan. Engineering recommends approval of the Drainage Report.

RESUBMITTAL REQUIRED: DP

APPROVAL: DR

The next submittal should address the following items:

GENERAL COMMENTS

1. The Drainage Report was reviewed for Development Plan purposes only.

2. A Grading Plan and Permit will be required.

3. Proposed developments exceeding 1 acre are subject to NPDES requirements. Contact Patricia Gilbert, 791-5550 for submittal requirements.

4. A Flood Use Permit is required prior to Grading Plan approval.

DEVELOPMENT PLAN

1. Per rezoning condition 2, dedication of right-of-way is required prior to Development Plan approval.

James C. Tate, P.E.
Civil Engineer
07/30/2003 FRODRIG2 PIMA COUNTY WASTEWATER Approved PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
August 22, 2003

TO: Steve Shields, Intertech Architectural Interiors, Inc.

THRU: Craig Gross, City of Tucson Development Services

FROM: Subhash Raval, P.E., Division Manager
Pima County Development Review & Technical Services Divisions

SUBJECT: Assistance League of Tucson Expansion
Development Plan - 2nd Submittal
D03-005



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Show the method and location of connection to the public sewer for the south structure.

2. Identify and label appropriately the sewer structure at the northeast corner of the property.

3. Based on the number of wastewater fixture units proposed for this project, a Sewer Service Agreement will not be required.

4. Please submit a blueline with the above revisions to Pima County Development Review for our files. No fee required for this submittal.

5. Subject to the above, we hereby approve the Development Plan.

If you wish to discuss the above comments, please contact Debbie Ketchem at 740-6404.




Subhash Raval, P.E., Division Manager
Pima County Development Review & Technical Services Divisions


SR/DK/dk
Copy: Project
07/30/2003 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D03-0005 ASSISTANCE LEAGUE EXPANSION/DEVELOPMENT PLAN
DATE: July 30, 2003



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Correct Lot 9 to Block 9 in Legal Description and Title Block.

2.) Number buildings numerically on Sheet 2.
08/05/2003 PETER MCLAUGHLIN ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
D03-005
Assistance League Expansion
Development Plan

TRANSMITTAL: August 5, 2003
DUE DATE: August 6, 2003

The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.


1. Please provide the following documentation to the Zoning Review Section for review: copy of the approved Pima County Assessor's Tax Combination Form.


2. Demonstrate compliance with rezoning condition 2 requiring right-of-way dedication along Alvernon Way.
DS 2-05.2.4.U

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
08/06/2003 JIM STOYANOFF COT NON-DSD REAL ESTATE Approved The legal description for r/w dedication is in for review with Engineering. Once I receive an approval from Engineering I will proceed with document preparation.
08/06/2003 JOE LINVILLE LANDSCAPE REVIEW Approved
08/06/2003 JIM STOYANOFF COT NON-DSD REAL ESTATE Approved R/W dedication has been recorded in docket 12132 at page 131, this completes Real Estates requirements.
08/08/2003 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D03-0005 Assistance League Expansion 08/07/03

( ) Tentative Plat
( X ) Development Plan
( X ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: C9-01-03, C10-87-98

NEIGHBORHOOD PLAN: Grant Alvernon

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: August 6, 2003

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
( X ) No Additional Comments - Complies With Planning Comments
Submitted on: 3/7/03

( X ) No Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: JBeall 791-4505 DATE: 8-7-03