Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: D03-0002
Parcel: 133452190

Review Status: Completed

Review Details: RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D03-0002
Review Name: RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2003 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/24/2003 PAUL MACHADO ENGINEERING REVIEW Approved To: Craig Gross DATE: September 24, 2003 Zoning Administrator

SUBJECT: East Pointe Commercial Center
Development Plan D03-0002 (Third Review)
T14S, R15E, Section 11

RESUBMITTAL REQUIRED: None.

Development Plan:

1. All comments have been addressed. The DP is approved be engineering.

Drainage Report:

1. The DR has been reviewed and approved for DP purposes.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
09/30/2003 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Plans Coordination Office
Development Services Department

PROJECT: D03-0002
Eastpointe Commercial Center, Lots 1-5
Development Plan

FROM: David Rivera
Senior Planner

FOR: Patricia Gehlen
Principal Planner
Zoning Review Section

TRANSMITTAL: September 30, 2003

DUE DATE: September 29, 2003

The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

1. Approval of the Scenic Corridor Application, SCZ-03-13.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

C:\planning\cdrc\developmentplan\D030002dpca.doc
10/02/2003 FRODRIG2 COT NON-DSD REAL ESTATE Approved All documents have been sent to the City Clerk for recordation.
10/02/2003 JOE LINVILLE LANDSCAPE REVIEW Approved
10/02/2003 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D03-0002 Eastpointe Commercial Center 09/30/03

() Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: S99-036, C9-83-09, C10-99-55

NEIGHBORHOOD PLAN: Pantano East Area Plan

GATEWAY/SCENIC ROUTE: Houghton Road Scenic Corridor

COMMENTS DUE BY: October 1, 2003

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on: 7/8/03
( ) No Resubmittal Required:
() Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Other

REVIEWER: JBeall791-4505 DATE: 9/23/03
COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D03-0002 Eastpointe Commercial Center 07/02/03

() Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: S99-036, C9-83-09, C10-99-55

NEIGHBORHOOD PLAN: Pantano East Area Plan

GATEWAY/SCENIC ROUTE: Houghton Road Scenic Corridor

COMMENTS DUE BY: July 8, 2003

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
( ) Resubmittal Required:
() Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Other

REVIEWER: JBeall791-4505 DATE: 7/1/03
Comprehensive Planning Task Force Comments
Eastpointe Commercial Center, D03-0002


The applicant’s request to develop the property located at the northwest corner of Houghton Road and Broadway Boulevard is subject to meeting certain rezoning and board of adjustment conditions.


15. The applicant’s comments appear to address the issue that the Houghton Greenway will only be built on the east side of Houghton Road, hence no need for a trail system. However, the applicant still needs to coordinate with Glenn Hicks at Parks and Recreation as to any possible contributing in lieu fees, as Houghton Greenway is a community trail system that benefits both sides of Houghton Road. Please provide documentation that this Houghton Greenway issue has been coordinated with Glenn Hick at Parks and Recreation.






































COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D03-0002 Eastpointe Commercial Center 02/10/03

() Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: S99-036, C9-83-09, C10-99-55

NEIGHBORHOOD PLAN: Pantano East Area Plan

GATEWAY/SCENIC ROUTE: Houghton Road Scenic Corridor

COMMENTS DUE BY: February 10, 2003

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
( ) Resubmittal Required:
() Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Other

REVIEWER: JBeall791-4505 DATE: 2/4/03
Comprehensive Planning Task Force Comments
Eastpointe Commercial Center, D03-0002


The applicant’s request to develop the property located at the northwest corner of Houghton Road and Broadway Boulevard is subject to meeting certain rezoning and board of adjustment conditions.

Provide updated Landscape Plan that is coordinated, compatible, and consistent with the revised Development Plan.

The revised development plan does not appear to provide, to the fullest extent possible, shade along pedestrian walkways within the proposed project site. Please show on the development plan [sheet 2] and the updated landscape plan [L1.1] the placement of trees along the interior pedestrian circulation paths of the project site so as to provide shade for pedestrians to the fullest extent possible. [Rezoning Condition no. 11]

There are duplicate rezoning conditions number 9 on the revised development plan, sheet 3. Please correct to remove duplication of rezoning condition number 9.

The rezoning conditions call for trees along the West property line to be at least 24 inch box in size. The development plan and the updated landscape plan do not indicate 24 inch box trees along the west property line, with the only reference in the landscape being 15 gallon trees. Please correct and add to the language in the updated Landscape plan to explicitly read that trees along the West property line shall be at least 24 inch box in size. [Rezoning Condition no. 1.K]

The development plan does not show or indicate that pedestrian access is restricted from Eastepointe Estates to the C-1 parcel at the drainage ways. Please provide a detail and indicate on the development how and where the pedestrian access is restricted from Eastepointe Estates to the C-1 parcel at the drainage ways. [Rezoning Condition no. 8]

The development plan does not show or indicate the buffer areas that shall be fenced before grading occurs in accordance with the approved NPPO. Please show on the development plan and/or the updated landscape plan the fencing for all the buffer areas in accordance with the approved NPPO. [Rezoning Condition no. 1.F]

The development plan does not appear to show that the retention/detention areas are to be fully landscaped and include trees, as well as, provide for water harvesting techniques. Please demonstrate and show on either the updated landscape plan and/or the development plan that the retention/detention areas will be fully landscaped to include trees with water harvesting techniques include in the landscape plan. [Rezoning Conditions, no. 1. O and P]

Defer to Traffic Engineering for comments and compliance of the following rezoning conditions: 2, 4, 5, and 6.

Defer to Floodplain Engineering for comments and compliance of the following rezoning conditions: 1. G, H, I.

Defer to Tucson Police Department for comments and compliance of the following rezoning condition: 12.

Defer to Development Services for comments and compliance of the following rezoning conditions: 1. F, D, E.

Provide renderings and color palette for all buildings and signage in order to demonstrate colors used are found in the surrounding natural desert. [Rezoning Condition no. 1.K]

The development plan, sheet 3, does not provide a section detail of the proposed masonry screen walls for this project. Please provide a section detail on sheet 3 of the development plan that includes design treatment and height dimensions for all masonry screen walls. [Rezoning Condition no. 7]

The Arizona Department of Transportation (ADOT) has initiated a Houghton Road Corridor Study to determine future improvements to Houghton Road from Sahuarita Road to Tanque Verde Road. ADOT has not yet made specific recommendations, but they have publicly stated that the future roadway will have limited access. The term, limited access, has been defined to limit access onto Houghton Road to major streets only. The two driveways along Houghton Road proposed in this development plan clearly do not represent limited access.

Since Houghton Road is a State Route for planning purposes, the design of the access onto Houghton Road should be reviewed and/or approved by ADOT before the revised development plan is approved by the City. Their review will also be required for any modifications to the median on Houghton Road.

As a limited access facility it can be expected that direct access from individual driveways will be extremely limited. This may mean that any access granted currently will be eliminated in the future. In consideration of this fact, the revised development plan, including on-site circulation, should be designed in a manner that provides all access and f circulation from Broadway Boulevard.

15. The Development Plan and updated Landscape Plan must delineate the approved Houghton Road cross-sections, including the urban trails system along the west side of the right-of-way. Please coordinate with Traffic Engineering, Vince Catalano, and Parks and Recreation, Glenn Hicks, and provide a section detail that shows the landscape cross-section, including urban trail system along Houghton Road.
10/06/2003 TIM ROWE PIMA COUNTY WASTEWATER Approved PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
October 15, 2003

TO: Bruce Paton, Rick Engineering

THRU: Craig Gross, City of Tucson Development Services

FROM: Subhash Raval, P.E., Division Manager
Pima County Development Review & Technical Services Division (Wastewater)

SUBJECT: Eastpointe Commercial Center, Lots 1-5
Development Plan - 3rd Submittal
D03-0002



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Pima County Wastewater Management Department hereby approves the above-referenced Development Plan as submitted.

If you wish to discuss the above comments, please contact me at 740-6585.




Subhash Raval, P.E., Division Manager
Pima County Development Review & Technical Services Division (Wastewater)


SR/SR/dk
Copy: Project
10/06/2003 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved NO COMMENTS.