Permit Number: D02-0036
Parcel: 133243740

Address:
280 N PANTANO RD

Review Status: Completed

Review Details: CDRC - DEVELOPMENT PLAN

Permit Number - D02-0036
Review Name: CDRC - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2002 FERNE RODRIGUEZ START INITIALIZE THE WORKFLOW Completed
10/23/2002 JIM EGAN CITY OF TUCSON - NOT DSD FIRE Approved THE DEVELOPMENT PLAN IS APPROVED 10/23/02
10/30/2002 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
D02-0036
ACORN ASSOCIATES ARCHITECTURE, LTD
HUGHES FEDERAL CREDIT UNION:
11/01/2002 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved 3950 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


Telephone: 520-884-3879
Fax: 520-770-2002
WR#65832 October 28, 2002


Mr. Kim Acorn
Acorn Associates Architecture, Ltd.
4400 E. Broadway, Suite #505
Tucson, AZ 85711

Dear Mr. Acorn:

SUBJECT: Hughes Federal Credit Union
D02-0036

Tucson Electric Power Company has reviewed and approved the development plan dated October 18, 2002. It appears that there are existing facilities within the boundaries of this project; however, they do not appear to be in conflict with this proposed development. In the event there are conflicts, the costs for relocation or removal will be borne by the developer.

The plan depicts a proposed 12’x35’ loading space crossing existing underground electrical facilities. If the grade is going to change due to the installation of the loading space, TEP will have to be notified to evaluate the conditions, and to decide if the facilities will need relocation.

Please submit a final set of plans including electrical load plans, to determine how TEP will serve this commercial development. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Greg Carter
Distribution Services – DS101
Tucson Electric Power Company
P. O. Box 711
Tucson, AZ 85702

Please call me at (520) 884-3879, should you have any questions.

Sincerely,


S. Glynda Rothwell
Right-of-Way Agent
Land Management

sgr
cc: City of Tucson
11/12/2002 JOE LINVILLE DEVELOPMENT SERVICES LANDSCAPE Denied The Landscape Section does not recommend approval of the Development Plan at this time.

The Native Plant Preservation application is approved.
Existing plants proposed to remain should be identified on the landscape plan.

The proposed loading zone and drive-through must be screened per LUC Table 3.7.2-I. Revise the landscape plan to identify all required screening elements and note the required height and basis for measurement. DS 2-07.2.2

Resubmittal of the Development Plan/Landscape Plan is required.
11/13/2002 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Craig and Ferne,
Attached is the transportation information for case #D02-0036. If you have any questions, please contact me.

Sandy White
Research & Statistical Analyst
Pima Association of Governments
ph: 520-792-1093 x508
fax: 520-792-9151
swhite@pagnet.org
11/13/2002 KAY MARKS PIMA COUNTY ADDRESSING Approved PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
201 N. Stone Ave, 1st Floor
Tucson, Arizona 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370



TO : CITY PLANNING
FROM : KAY MARKS, ADDRESSING OFFICIAL
SUBJECT : D02-0036 HUGHES FEDERAL CREDIT UNION/REVISED DEVLOPMENT PLAN
DATE : November 4, 2002


***********************************************************************************************************

The above referenced project has been reviewed by this Division for all matters pertaining to street naming/ addressing, and we hereby approve this project.




1. Submit a 24 x 36 Mylar of approved Development Plan to City Planning. Signed and dated mylar will be forwarded to Pima County Addressing prior to the assignment of addresses.

2. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
11/13/2002 GLENN HICKS CITY OF TUCSON - NOT DSD PARKS & RECREATION Approved DATE: November 8, 2002

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks,Parks and Recreation

RE: CDRC Transmittal, Project D02-0036 Hughes Federal Credit Union

CC: Craig Gross, Development Services


Staff has reviewed and approved.
11/19/2002 DAN CASTRO DEVELOPMENT SERVICES ZONING Denied COMMENTS
CODE SECTION/ DEVELOPMENT STANDARD

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is October 21, 2003.

2. List the name of the developer of the project.
D.S. 2-05.2.2.A.1

3. Add the development plan case number (D02-0036) to the lower right corner of each sheet on all plans.
D.S. 2-05.2.2.B.2

4. Under development data block on sheet DP1, add the applicable 'subject to" LUC section 3.5.4.5.A to the proposed use note.
D.S. 2-05.2.2.B.3

5. Add the following general note: "This project is designed to meet the Major Streets and Routes (MS&R) Setback Zone criteria."
D.S. 2-05.2.2.B.10

6. Provide a continuous on-site pedestrian circulation path connecting the proposed building and all other buildings in the shopping center. Refer to D.S. 2-08 for criteria.
D.S. 2-05.2.4.K

7. Development data note number five (5) on sheet DP1 states that the approved development plan for this site included a surplus of 11 spaces. The last approved development plan in City Records (C12-88-3) indicates that a total of 818 vehicle parking spaces are required and 821 are provided for the shopping center. Revise development data note number five (5) to reflect the correct number of surplus parking spaces as shown on the last approved development plan. In addition, please provide the vehicle parking calculation for the entire shopping center to verify the correct number of vehicle parking spaces required and provided.
D.S. 2-05.2.4.P

8. If applicable, provide a detail of existing and/or proposed free-standing signage and outdoor lighting on the development plan.
D.S. 2-05.2.4.W

9. All requested changes must be made to the development and landscape plans.
D.S. 2-07.2.1.A
11/20/2002 FRODRIG2 CITY OF TUCSON - NOT DSD REAL ESTATE Approved No objection.
11/21/2002 ROGER HOWLETT CITY OF TUCSON - NOT DSD COMMUNITY PLANNING Approved COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D02-0036 Hughes Federal Credit Union 11/21/02

() Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C12-88-3

NEIGHBORHOOD PLAN: Pantano East Area Plan

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: November 18, 2002

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
( ) No Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: JBeall 791-4505 DATE: 11-21-02

Comprehensive Planning Task Force Comments
Hughes Federal Credit Union, D02-0036



The conditions from the rezoning case C12-88-3 required a five-foot wall between the commercial and residential areas. Please indicate on Development Plan the wall height for the perimeter walls that abut residential properties; and include a note in the General Notes section to read “All walls visible are to be graffiti-resistant and incorporate one or more visually appealing design treatments, such as: the use of two or more decorative materials like stucco, tile, stone, or brick; a visually interesting design on the wall surface; varied wall alignments (jog, curve, notch, setback, etc.); and/or, trees and shrubbery in voids created by wall variations.”

Please provide a note to the General Notes section that reads “Entryways, exit doors, areas around windows and loading docks will have lighting to provide – minimum maintained average of 0.5 foot candles. [Reference C12-88-3]
11/22/2002 ZELIN CANCHOLA CITY OF TUCSON - NOT DSD TRAFFIC Denied Traffic Engineering recommends DISAPPROVAL of this development plan

1. Use standard symbols as delineated in SD100, 1994 Ed PC/COT Standard Details for Public Improvements
2. If details 10, 11 on sheet 4 are not used, then why list them?

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dkelch1@ci.tucson.az.us
11/25/2002 PAUL MACHADO DEVELOPMENT SERVICES ENGINEERING Denied To: Craig Gross
Project Manager
SUBJECT: Hughes Federal Credit Union, 280 N. Pantano Rd.
Development plan D02-0036 (First Review)
T14S, R15E, Section 09


RESUBMITTAL REQUIRED: Development Plan

The Development Plan (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please provide existing topograpghic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23 and D.S. 2-05.2.1.H.
2. Obtain permission from Solid Waste to use existing refuse collection bin.
3. A separate grading permit may be required.
4. Fully-dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
5. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
6. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21 and D.S. 2-05.2.3.C.
7. Show Development plan number on all sheets per D.S. 2-02.2.1.29.
8. A private improvement agreement may be necessary for work performed within the Right-of-way. Contact Department of transportation at (520) 791-4249 for information.
9. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
10. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks via scuppers. Please provide supporting calculations to demonstrate compliance with D.S 3-01.4.4. If the roof drains have not been finaled, a general note indicating scuppers are needed per COT/ SD under side walks would suffice.
11. Add a note "Depress all landscaped areas a maximum of 6" for water harvesting".
12. Draw locations and indicate types of off-site runoff acceptance points and/or on-site runoff discharge points per D.S. 2-05.2.1.H.7
13. List rezoning conditions on DP, if applicable.

Drainage Report:
1. The Drainage report is approved.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate,
12/12/2002 TIM ROWE PIMA COUNTY WASTEWATER Approv-Cond COMMENTS OF FILE