Permit Number: D02-0034
Parcel: 133243690

Address:
100 N PANTANO RD

Review Status: Completed

Review Details: CDRC RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D02-0034
Review Name: CDRC RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2003 FRODRIG2 COT NON-DSD REAL ESTATE Needs Review
12/02/2002 FERNE RODRIGUEZ START INITIALIZE THE WORKFLOW Completed
12/03/2002 KAY MARKS PIMA COUNTY ADDRESSING Approved PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
201 N. Stone Ave, 1st Floor
Tucson, Arizona 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370



TO : CITY PLANNING
FROM : KAY MARKS, ADDRESSING OFFICIAL
SUBJECT : D02-0034 DEPARTMENT STORE / DEVELOPMENT PLAN
DATE : December 3, 2002




The above referenced project has been reviewed by this Division for all matters pertaining to street naming/ addressing, and we hereby approve this project.

Approved on condition that recorded legal for Broadway Pantano Center is added to Title Block on approved mylar.

NOTE:

1. Submit a 24 x 36 Mylar of approved Development Plan to City Planning. Signed and dated mylar will be forwarded to Pima County Addressing prior to the assignment of addresses.

2. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
12/10/2002 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved Traffic Engineering approves the development plan D02-0034 based on the traffic study addendum which states one of the access points from the development remain open to Centrepark Drive.
12/10/2002 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
December 05, 2002

TO: Craig Hunt, Entranco

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Department Store - Broadway Pantano Center
Development Plan - 1st and 2nd Submittals
D02-0034



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Due to an extensive backlog of plans to review, we received the second submittal of the development plan, before we had reviewed the first submittal. The second submittal was reviewed in the first submittal’s place in our queue of plans to review. The following comments apply to the second submittal.

2. There is currently capacity in the existing downstream sewerage system for this development. This response is not to be construed as a commitment for conveyance capacity allocation, but rather an analysis of the existing sewerage system as of this date.

3. Based on the preliminary sewer layout as shown on the referenced development plan, this project would qualify for Non-Participating sewer connection fee rates.

4. The development plan is hereby approved, subject to the following:

5. Sheet 1: Delete General Note 13. This information is understood from S02-011.

6. Sheet 3 & 5: Revise the area of the trash compactor to what was shown on the first submittal of the development plan (i.e. slab on grad, and with no retaining walls or handrails) as stated in your 12/04/02 e-mail message to me.

7. Sheet 5: Show the plan number (G-2002-084) for the public sewer line on the west side of the building.

Please note that G-2002-084 has not yet been tested or accepted for use by PCWWM. No connection may be made to this sewer line, until after it has been tested and accepted for use by PCWWM.

8. Please contact Mr. Glen Hitz of the Pima County Wastewater Management (PCWWM) Department at 740-6547 to determine if written authorization from PCWWM is necessary to place the trash compactors within the public sewer easement.

If you wish to discuss the above comments, please contact me at 740-6563.




Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division


TR/tr

Copy: Project








PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
December 05, 2002

TO: Craig Hunt, Entranco

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Department Store - Broadway Pantano Center
Development Plan - 1st and 2nd Submittals
D02-0034



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Due to an extensive backlog of plans to review, we received the second submittal of the development plan, before we had reviewed the first submittal. The second submittal was reviewed in the first submittal’s place in our queue of plans to review. The following comments apply to the second submittal.

2. There is currently capacity in the existing downstream sewerage system for this development. This response is not to be construed as a commitment for conveyance capacity allocation, but rather an analysis of the existing sewerage system as of this date.

3. Based on the preliminary sewer layout as shown on the referenced development plan, this project would qualify for Non-Participating sewer connection fee rates.

4. The development plan is hereby approved, subject to the following:

5. Sheet 1: Delete General Note 13. This information is understood from S02-011.

6. Sheet 3 & 5: Revise the area of the trash compactor to what was shown on the first submittal of the development plan (i.e. slab on grad, and with no retaining walls or handrails) as stated in your 12/04/02 e-mail message to me.

7. Sheet 5: Show the plan number (G-2002-084) for the public sewer line on the west side of the building.

Please note that G-2002-084 has not yet been tested or accepted for use by PCWWM. No connection may be made to this sewer line, until after it has been tested and accepted for use by PCWWM.

8. Please contact Mr. Glen Hitz of the Pima County Wastewater Management (PCWWM) Department at 740-6547 to determine if written authorization from PCWWM is necessary to place the trash compactors within the public sewer easement.

If you wish to discuss the above comments, please contact me at 740-6563.




Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division


TR/tr

Copy: Project








PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
December 05, 2002

TO: Craig Hunt, Entranco

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Department Store - Broadway Pantano Center
Development Plan - 1st and 2nd Submittals
D02-0034



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Due to an extensive backlog of plans to review, we received the second submittal of the development plan, before we had reviewed the first submittal. The second submittal was reviewed in the first submittal’s place in our queue of plans to review. The following comments apply to the second submittal.

2. There is currently capacity in the existing downstream sewerage system for this development. This response is not to be construed as a commitment for conveyance capacity allocation, but rather an analysis of the existing sewerage system as of this date.

3. Based on the preliminary sewer layout as shown on the referenced development plan, this project would qualify for Non-Participating sewer connection fee rates.

4. The development plan is hereby approved, subject to the following:

5. Sheet 1: Delete General Note 13. This information is understood from S02-011.

6. Sheet 3 & 5: Revise the area of the trash compactor to what was shown on the first submittal of the development plan (i.e. slab on grad, and with no retaining walls or handrails) as stated in your 12/04/02 e-mail message to me.

7. Sheet 5: Show the plan number (G-2002-084) for the public sewer line on the west side of the building.

Please note that G-2002-084 has not yet been tested or accepted for use by PCWWM. No connection may be made to this sewer line, until after it has been tested and accepted for use by PCWWM.

8. Please contact Mr. Glen Hitz of the Pima County Wastewater Management (PCWWM) Department at 740-6547 to determine if written authorization from PCWWM is necessary to place the trash compactors within the public sewer easement.

If you wish to discuss the above comments, please contact me at 740-6563.




Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division


TR/tr

Copy: Project
12/13/2002 PETER MCLAUGHLIN DEVELOPMENT SERVICES ZONING Approv-Cond APPROVED BY LANDSCAPE
12/13/2002 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D02-0034 Department Store 12/11/02

() Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
( ) Site Plan

CROSS REFERENCE: S02-011, C9-00-39, SE-01-28

NEIGHBORHOOD PLAN: Pantano East

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: December 16, 2002

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on: 11-15-02
() No Resubmittal Required:
() Tentative Plat
( ) Development Plan
() Landscape Plan
( ) Site Plan

REVIEWER: JBeall DATE: 12-10-02
COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application
12/13/2002 PETER MCLAUGHLIN DEVELOPMENT SERVICES ZONING Approv-Cond TO: Development Services Department Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: D02-034
Broadway Pantano Center
Lots 4, (5) and 6
199 N. Pantano Road
Development Plan

TRANSMITTAL: December 13, 2002
DUE DATE: December 16, 2002

The Zoning Review Section approves the development plan for this project, subject to the following change on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.


1. Provide recordation information for the two new utility easements. All proposed easements must be recorded and recordation information added to the plan prior to approval.
DS 2-05.2.3.B

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
12/16/2002 PAUL MACHADO DEVELOPMENT SERVICES ENGINEERING Approved APPROVED BY LANDSCAPE
12/16/2002 PAUL MACHADO DEVELOPMENT SERVICES ENGINEERING Approved To: Craig Gross
Project Manager

SUBJECT: New Department Store-Pantano and Broadway Center
D02-0034 (Second Review)
T14S, R15E, Section 08


RESUBMITTAL REQUIRED: None


Development Plan:

All necessary comments have been addressed. The Development plan is now approved.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate,
12/16/2002 JOE LINVILLE DEVELOPMENT SERVICES LANDSCAPE Approved APPROVED BY LANDSCAPE