Permit Number: D02-0028
Parcel: 140410770

Review Status: Completed

Review Details: CDRC RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D02-0028
Review Name: CDRC RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2002 FERNE RODRIGUEZ START INITIALIZE THE WORKFLOW Completed
10/09/2002 BLANCA ESPINO DEVELOPMENT SERVICES ENGINEERING Approved To: Craig Gross DATE: March 14, 2002
CDRC Coordinator
FROM: Blanca Espino, Engineering Associate

SUBJECT: Engineering review of the Development Plan and Drainage Statement. The activity number is D02-0028.

SUMMARY: The Development Plan and Drainage Statement were received by Engineering for second review on October11, 2002. Engineering recommends approval of the Development Plan and Drainage Statement after condition has been received.

Submit two dimensioned cross sections of the proposed Detention/Retention Basin and a dimensioned detail of the proposed trench with wse and grate/cover.








Blanca Espino
Engineering Associate
10/09/2002 BLANCA ESPINO DEVELOPMENT SERVICES ENGINEERING Approved Universal Avionics meet conditions therefore, the Development Plan D02-0028 is Approved.
10/09/2002 JOE LINVILLE DEVELOPMENT SERVICES LANDSCAPE Approved The Landscape Section recommends approval of the Development Plan.
10/10/2002 KAY MARKS PIMA COUNTY ADDRESSING Approved PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
201 N. Stone Ave, 1st Floor
Tucson, Arizona 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370



TO : CITY PLANNING
FROM : KAY MARKS, ADDRESSING OFFICIAL
SUBJECT : D02-0028 UNIVERSAL AVIONICS / REVISED DEVELOPMENT PLAN
DATE : October 10, 2002


***********************************************************************************************************

The above referenced project has been reviewed by this Division for all matters pertaining to street naming/ addressing, and we hereby approve this project.


NOTE:

1. Submit a 24 x 36 Mylar of approved Development Plan to City Planning. Signed and dated mylar will be forwarded to Pima County Addressing prior to the assignment of addresses.

2. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
10/11/2002 DAN CASTRO DEVELOPMENT SERVICES ZONING Approv-Cond The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

1. The Pima County Assessor Combo Request form submitted with the plans has not been approved by the Assessors office. Please submit a copy of the approved combo form.
10/16/2002 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved 3950 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


Telephone: 520-884-3879
Fax: 520-770-2002
WR#93664 October 16, 2002


Mr. Kevin Morrow
Gromatzky Dupree and Assoc. Southwest
4811 East Grant Road, Suite 261
Tucson, Arizona 85712

Dear Mr. Morrow:

SUBJECT: Universal Avionics
D02-0028

Tucson Electric Power Company has reviewed and approved the resubmittal of the Development Plan. It appears that there are no existing facilities or conflicts within the boundaries of this proposed development.

Please submit a final set of plans, including electrical load plans, to determine how TEP will serve this commercial development. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Randy Alday
Distribution Services – DS-301
Tucson Electric Power Company
P. O. Box 711
Tucson, AZ 85702

Please call me at (520) 884-3879, should you have any questions.

Sincerely,



S. Glynda Rothwell
Right-of-Way Agent
Land Management

sgr

cc: Craig Gross, City of Tucson
10/18/2002 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMMUNITY PLANNING AND PRESERVATION COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D02-0028 Universal Avionics 10/16/02

( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C15-88-1

NEIGHBORHOOD PLAN: General Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: October 21, 2002

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on: 9-12-02
( ) No Resubmittal Required
() Tentative Plat
( ) Development Plan
() Landscape Plan
() Other

REVIEWER: JBeall DATE: 10-14-02
COMMUNITY PLANNING AND PRESERVATION COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D02-0028 Universal Avionics 09/12/02

( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C15-88-1

NEIGHBORHOOD PLAN: General Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: September 26, 2002

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() No Resubmittal Required
() Tentative Plat
( X ) Development Plan
() Landscape Plan
() Other

REVIEWER: JBeall DATE: 9-6-02

Community Planning and Preservation Comments
Universal Avionics, D02-0028



This development plan must be in compliance with annexation zoning conditions from ordinance no. 7025 adopted on September 6, 1988, Country Club/Valencia annexation district.


1. The proposed project site as indicated on the zoning base maps has a zoning classification of, I-1 ®, which is subject to the following conditions:

4. The I-1 ® portions shall be limited to a height of 39 feet and restricted by prohibiting the uses in Attachment B. [Zoning Ordinance No. 7090]

Please address these conditions on the development plan in the General Notes section by including the following notes:

The maximum building height is to be restricted to 39 feet, per zoning ordinance 7090.

(30) The following uses are prohibited in I-1 zoning as part of zoning ordinance 7090, see Attachment B for prohibited uses.
10/23/2002 FRODRIG2 PIMA COUNTY WASTEWATER Approved PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
October 23, 2002

TO: Kevin Morrow, GDA Southwest, L.L.C.

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Universal Avionics
Development Plan - 2nd Submittal
D02-0028



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Pima County Wastewater Management Department hereby approves the above-referenced Development Plan.

If you wish to discuss the above comments, please contact Tim Rowe at 740-6563.




Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

TR/DK/dk
Copy: Project