Permit Number: D02-0013
Parcel: 127102290

Address:
601 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D02-0013
Review Name: RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/19/2004 JIM EGAN COT NON-DSD FIRE Approved The revised Development Plan is approved October 19, 2004.
10/26/2004 JCLARK3 ENV SVCS REVIEW Denied * Plan mentioned 10 x 10 enclosure. The 10 x 10 area should be the clear area between the bollards inside the enclosure.
* No detail for the enclosure shown. Enclosure called out in the Development Standards specifies the 10 feet clear area, doors and a 10 foot concrete slab in front of the enclosure.
* The west enclosure of the two enclosures west of building one has a conflict for service. The collection vehicle is unable to be positioned in the required 14 foot by 40 foot required clear area in front of the enclosure. If this enclosure is positioned at a 30 Degree angle to the PAAL the enclosure clear area would not be in conflict and could be serviced.
11/01/2004 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMMUNITY PLANNING AND PRESERVATION COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D02-0013 5th & Wilmot Corporate Offices 11/01/04

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-00-19, C12-75-12

NEIGHBORHOOD PLAN: Sewell-Hudlow Neighborhood Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: November 7, 2002

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: October 11, 2002
11/02/2004 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this revised DP.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
11/04/2004 ELAINE ROSE ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
D02-013
5th & Wilmot Corporate Offices
Development Plan revisions

TRANSMITTAL: November 4, 2004
DUE DATE: November 2, 2004

1. Revise the bicycle parking calculation to be based on the vehicle parking provided rather than that required. Eight percent of 511 equals 41 bicycle parking spaces required.
DS 2-05.2.4.Q

2. Add the dimensions and height of the garage along with the MS&R building setback for the garage (dimensioned from back of curb location) from 5th Street. DS 2-05.2.4.I

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
12/23/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed
12/23/2004 MATT FLICK ENGINEERING REVIEW Denied Threshold Retention

Although the site is not in a designated balanced or critical basin, the site is subject to threshold retention since it is a commercial site greater than 1 acre. Demonstrate compliance with threeshold retention requirements.