Permit Number: D01-0013
Parcel: 10309068D

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D01-0013
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2006 MARILYN KALTHOFF START PLANS SUBMITTED Completed
12/14/2006 KAROL ARAGONEZ ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D01-0013
North Tucson Business Center
Development Plan Resubmittal

TRANSMITTAL DATE: December 14, 2006

DUE DATE: December 12, 2006

COMMENTS:

The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 1197.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D01-0013dpr1.doc
12/21/2006 JASON GREEN ENGINEERING REVIEW Denied DATE: December 21, 2006
SUBJECT: Engineering review of North Tucson Business Center - Development Plan
TO: Patricia Gehlen, CDRC Manager
LOCATION: 3745 E I-10 Frontage Road, T13S R13E Sec33, Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: D01-0013


SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised development plan addendum, drainage report, landscape plan, cross access agreements, and the original development plan, Sheets 1 thru 2, and does not recommend approval of the development plan addendum at this time. The following items need to be addressed:


DRAINAGE REPORT:

1) DS Sec.10-02.14.5.8: Dry wells are highly discouraged due to their high failure rates, in order to help ensure that this exiting dry well functions now and in the future provide percolation test results to verify performance of the existing dry well. Provide estimate of the volume for the dry well to verify that the 2,000 gallons of water used to perform the test was enough to fill the dry well chamber and a portion of the basin in order to assure that percolation rates drain within the maximum 12-hour period. During the percolation test, the dry well shall be filled with clean water until the rate of inflow and the percolation rate have stabilized for a period of one hour. If a rate of inflow below that required is obtained, then additional dry wells will be required.

2) DS Sec.10-01.3.5.1.3: Maximum disposal times of stormwater runoff for a detention basin that intercepts runoff from an upstream watershed area which is up to 10-acres in size is 12 hours. The addendum provided by Terracon for the drywell testing shows that the percolation tests were performed using a 24-hour drain down time. Revise the percolation test to meet the standards needed in item 1 and to show that the drain down time for this retention basin is 12-hours or provide an offsite watershed map with a delineation of the watershed showing that it is greater than 10-acres, then a 24-hour maximum disposal time can be used for the percolation test.


GENERAL COMMENTS:

Provide a revised geotechnical addendum and/or a revised watershed delineation within the drainage report at re-submittal.

The revised geotechnical addendum and percolation test must address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

If you have any questions, or to schedule an appointment, I can be reached at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
12/22/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

December 22, 2006


South Western Consulting Engineers LLC
435 East 9th Street
Tucson, AZ 85705

Subject: D01-0013 North Tucson Business Center Lost 2 & 3 Revised Development Plan

Dear Steve:

Your submittal of November 13, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

2 Copies Revised Development Plan (Engineering, DSD)

2 Copies Revised Drainage Report/Geotechnical Addendum (Engineering, DSD)





Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 628-1063