Plan Number: TW-WCP-1023-00116
Parcel: 13213034D

Review Status: Requires Resubmit

Review Details: WATER DESIGN PLAN REVIEW v.3

Plan Number - TW-WCP-1023-00116
Review Name: WATER DESIGN PLAN REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TW Managerial Review PENDING ASSIGNMENT
TFD Review & Signature REQUIRES RESUBMIT Update plans to correct fire flow required in accordance with IFC 2018, B105.1(2), including reductions for sprinkler systems.
I assume this will be 1500gpm for 2 hours.
Questions: patricia.shelton@tucsonaz.gov
TW Design Plan Review REQUIRES RESUBMIT SEE REDLINE - NEEDS MASTER WATER PLAN REVISED
TW Issue Invoice REVIEW COMPLETED
TW Verify Fees Paid REVIEW COMPLETED