Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Requires Resubmit
Review Details: WATER DESIGN PLAN REVIEW v.3
Plan Number - TW-WCP-1023-00116
Review Name: WATER DESIGN PLAN REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
TW Managerial Review | PENDING ASSIGNMENT | ||||
TFD Review & Signature | REQUIRES RESUBMIT | Update plans to correct fire flow required in accordance with IFC 2018, B105.1(2), including reductions for sprinkler systems. I assume this will be 1500gpm for 2 hours. Questions: patricia.shelton@tucsonaz.gov |
|||
TW Design Plan Review | REQUIRES RESUBMIT | SEE REDLINE - NEEDS MASTER WATER PLAN REVISED | |||
TW Issue Invoice | REVIEW COMPLETED | ||||
TW Verify Fees Paid | REVIEW COMPLETED |