Review Details: WATER DESIGN PLAN REVIEW v.1
Plan Number - TW-WCP-0625-00033
Review Name: WATER DESIGN PLAN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| TW Managerial Review | PENDING ASSIGNMENT | ||||
| TFD Review & Signature Fast | REQUIRES RESUBMIT | The fire flow requirement for this fully sprinkler'd building (Type II-B, 130,249 sq. ft.) would be 2,000 gpm for 2 hours. See 2024 IFC, Table B105.1(2) Questions: patricia.shelton@tucsonaz.gov |
|||