Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: TW-PLAN-0826-0155
Parcel: Unknown

Address:
4498 W INA RD

Review Status: Requires Resubmit

Review Details: TWPE 60% DESIGN REVIEW v.1

Plan Number - TW-PLAN-0826-0155
Review Name: TWPE 60% DESIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TWPE Construction APPROVED
TWPE Project Managers REQUIRES RESUBMIT
TWPE Project Supervisor Oversight REQUIRES RESUBMIT
TWPE Cathodic Protection REVIEW COMPLETED
TWPE Civil Engineers (CE) REVIEW COMPLETED
TWPE Engineering Manager Oversight REVIEW COMPLETED Comments were provided during internal meeting with TW on 9/3. Comments included considering a revised alignment at the treatment facility, looking at placing the conveyance line in the alley instead of going out to Camino de O Oeste. Additionally, consultant shall consider revising the alignment on Mars St to follow the northern edge, maintaining sufficient offset so that the trench limits for the pipe lay outside of the curb&gutter/wedge curb.
TWPE Maintenance REVIEW COMPLETED
TWPE Pipeline Protection REVIEW COMPLETED
TWPE Senior Engineering Associates (SEA) REVIEW COMPLETED
TWPE System Planning REVIEW COMPLETED SP hydraulic analysis attached. 12-inch TM is sufficient for 1000 gpm design flow from Well Z-014C.