Plan Review Detail
Review Status: Requires Resubmit
Review Details: TWPE AS-BUILT REVIEW v.1
Plan Number - TW-PLAN-0326-0072
Review Name: TWPE AS-BUILT REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| TWPE Engineering Chief - Authorization | REQUIRES RESUBMIT | TW-PLAN-0326-0072 Ft Lowel Park Rec Meter “As-builts) 1) Sheet 1: Add PJW926 as project number 2) Sheet 1: Add inspectors block 3) Sheet 1: Is this plan set 100% for review as denoted or are these as-builts? 4) Sheet 1: add TW-PLAN-0326-0072 5) Sheet 2: Key not 13. Plans will not be signed or approved until all necessary easements have been recorded |
|||
| TWPE Civil Engineers (CE) | REVIEW COMPLETED | See the comments in the drawing | |||
| TWPE Engineering Manager Oversight | REVIEW COMPLETED | Resubmittal Required | |||
| TWPE Project Managers | REVIEW COMPLETED |