Plan Review Detail
Review Status: In Review
Review Details: TWPE 100% DESIGN PLAN APPROVAL v.1
Plan Number - TW-PLAN-0326-0017
Review Name: TWPE 100% DESIGN PLAN APPROVAL v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| TWPE Operations | APPROVED | ||||
| TWPE Security | APPROVED | ||||
| TWPE Civil Engineers (CE) | PENDING ASSIGNMENT | ||||
| TWPE Deputy Director - Authorization | PENDING ASSIGNMENT | ||||
| TWPE Resource Planning | PENDING ASSIGNMENT | ||||
| TWPE Senior Engineering Associates (SEA) | PENDING ASSIGNMENT | ||||
| TWPE Water Quality Lab | PENDING ASSIGNMENT | ||||
| TWPE Engineering Chief - Authorization | REQUIRES RESUBMIT | TW-PLAN-0325-0017 AWP Demo 1) Special Specifications page 010302 Permitting Requirements. a. Jacobs is obtaining the required Grading and Building permits for this project. b. Following paragraph indicates that a paper process is used, permit submittal and review is all digital. 2) Special Specifications 010720 Project Record Documents. This stated process is out of date and should be updated to reflect plan revisions submittals and reviews electronically 3) 100% Plans. Sheet 42 detail 2. 4” over 8” for the paving cross section is not necessary. Change parking area to 2” over 4” and PAAL to 3” over 6”, reference City of Tucson Technical Standards Manual section 10-01-3.1 4) Please resolve other comments on plans from staff as applicable. |
|||
| TWPE Project Supervisor Oversight | REQUIRES RESUBMIT | ||||
| TFD Review & Signature Fast | REVIEW COMPLETED | ||||
| TWPE Electrical | REVIEW COMPLETED | ||||
| TWPE GSI Green Stormwater Infrastructure | REVIEW COMPLETED | Approved - No new comments from S2S team | |||
| TWPE Instrumentation | REVIEW COMPLETED | ||||
| TWPE Maintenance | REVIEW COMPLETED | ||||
| TWPE Project Managers | REVIEW COMPLETED | FROM: Ramiro Olivarez *Please note these are not official Zoning Review Section Comments but are comments PDSD may require in their review. * SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) COMMENT: Upon formal submittal to PDSD separate the Development Package sheets from the Construction Plan sheets. The proposed development must comply with the City of Tucson Unified Development Code (UDC) Administrative Manual Chapter 2-06 – Development Package. 2-06.3.0 FORMAT REQUIREMENTS 1. COMMENT: 2-06.3.12 - Upon formal submittal to PDSD separate the Development Package sheets from the Construction Plan sheets. The proposed development must comply with the City of Tucson Unified Development Code (UDC) Administrative Manual Chapter 2-06 – Development Package. CONTENT REQUIREMENTS 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. Zoning and Land Use Notes 2-06.4.7.A.1 - List as a general note: "Existing zoning is ____." 2. COMMENT: 2-06.4.7.A.1 - Include the information as noted by the Standard above. Be aware this proposed use/project is in an RX-1 Zone and is a nonconforming use. Formal comments such as a CMO Waiver from PDSD on how to proceed will be required in the Development Package submittal. 3. Comment: List the use of the project and use specific standards. A Zoning Examiner Special Exception Procedure may be required based on formal PDSD comments. 4. COMMENT: 2-06.4.8.A - Include the information as noted by the Standard above. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 5. COMMENT: 2-06.4.9.H.5 - Include the information as noted by the Standard above. 6. COMMENT: A back-up spur must be provided at the end of a row of parking if no ingress or egress is provided at that end. 7. COMMENT: The spur must be a minimum of three feet in depth and have a three foot radii and a wheel barrier to prevent encroachment onto any unsurfaced areas. 8. COMMENT: A minimum distance of three (feet must be provided between the back of spur and any wall, screen, or other obstruction over six inches in height. 9. COMMENT: When bollards or architectural features are used to provide physical separation, the maximum separation between the barriers is five feet clear. 10. COMMENT: Ensure a minimum of two and one-half feet from the front of all the parking spaces. 11. COMMENT: A motor vehicle space must have a minimum width of ten feet when the side(s) of the parking space abuts a vertical barrier over six inches in height. 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 12. COMMENT: 2-06.4.9.H.5.a - Include the information as noted by the Standard above. 13. COMMENT: Provide a typical motor vehicle off-street parking space detail. ***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations *** |
|||
| TWPE Public Information Planning | REVIEW COMPLETED | ||||
| TWPE System Controls | REVIEW COMPLETED | Please see 100% Review Notes in Attachments | |||
| TWPE System Planning | REVIEW COMPLETED |