Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: WATER MASTER PLAN - SINGLE PHASE v.1

Plan Number - TW-MWP-1124-00064
Review Name: WATER MASTER PLAN - SINGLE PHASE v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TW Hydraulic Modeling Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TW Administrative Completeness REQUIRES RESUBMIT The Master Plan submittal is incomplete and is missing the following information:

- Proposed spot grades at all tees, hydrants, DVA, and all commercial and irrigation water services are missing from the plan per design requirement item 3 of the checklist.

- 3-inch service lines are not permitted. Please change to 4-inch service line with 3-inch meter.

-Looping of the new water system is required where feasible. Please eliminate the dead end or explain reasoning why looping of the water system is not feasible per design requirement item 12 of the checklist.
TFD MWP Initial Review Fast REVIEW COMPLETED