Plan Number: TW-MWP-1024-00058
Parcel: 14106009J

Address:
6251 S KOLB RD

Review Status: Requires Resubmit

Review Details: WATER MASTER PLAN - SINGLE PHASE v.1

Plan Number - TW-MWP-1024-00058
Review Name: WATER MASTER PLAN - SINGLE PHASE v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TW Administrative Completeness PENDING ASSIGNMENT
TW Hydraulic Modeling Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TFD MWP Initial Review REQUIRES RESUBMIT Please update Master Water Plan to include the Fire Flow demand. Since all buildings are provided with fire sprinklers, the required fire flow would be 1500gpm for 2 hours in accordance with the 2024 IFC, Appendix B, and Tucson Water Design Standards.