Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Requires Resubmit
Review Details: WATER MASTER PLAN - SINGLE PHASE v.1
Plan Number - TW-MWP-1024-00058
Review Name: WATER MASTER PLAN - SINGLE PHASE v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
TW Administrative Completeness | PENDING ASSIGNMENT | ||||
TW Hydraulic Modeling Review | PENDING ASSIGNMENT | ||||
TW Issue Invoice | PENDING ASSIGNMENT | ||||
TW Managerial Review | PENDING ASSIGNMENT | ||||
TW Verify Fees Paid | PENDING ASSIGNMENT | ||||
TFD MWP Initial Review | REQUIRES RESUBMIT | Please update Master Water Plan to include the Fire Flow demand. Since all buildings are provided with fire sprinklers, the required fire flow would be 1500gpm for 2 hours in accordance with the 2024 IFC, Appendix B, and Tucson Water Design Standards. Questions: patricia.shelton@tucsonaz.gov |