Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Plan Number: TW-MWP-1023-00072
Parcel: 10821014H
Review Status: Requires Resubmit
Review Details: WATER MASTER PLAN - SINGLE PHASE v.1
Plan Number - TW-MWP-1023-00072
Review Name: WATER MASTER PLAN - SINGLE PHASE v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
TW Hydraulic Modeling Review | PENDING ASSIGNMENT | ||||
TW Issue Invoice | PENDING ASSIGNMENT | ||||
TW Managerial Review | PENDING ASSIGNMENT | ||||
TW Verify Fees Paid | PENDING ASSIGNMENT | ||||
TW Administrative Completeness | REQUIRES RESUBMIT | Fire flow on this project does not meet Tucson Water's Minimum design standards and is in direct violation of Tucson Water Design Standard 8-06.3.2B which requires a minimum fire flow of 1000 gpm for 2 hours. In addition, we will not accept two parallel 6 and 4 inch lines in close proximity to each other. Please revise the plan to have a single pipeline. Finally, the water availability letter for this project has expired. Please submit an updated letter with your next submittal. | |||
TFD MWP Initial Review | REVIEW COMPLETED |