Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: WATER MASTER PLAN - SINGLE PHASE v.2

Plan Number - TW-MWP-1023-00072
Review Name: WATER MASTER PLAN - SINGLE PHASE v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TW Hydraulic Modeling Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TW Administrative Completeness REQUIRES RESUBMIT Fire flow on this project does not meet Tucson Water's Minimum design standards and is in direct violation of Tucson Water Design Standard 8-06.3.2B which requires a minimum fire flow of 1000 gpm for 2 hours. In addition spot Grade elevation is missing for the Fire Hydrant Lateral.