Review Date Reviewer's Name Type of Review Description Status Comments
TW Hydraulic Modeling Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TW Administrative Completeness REQUIRES RESUBMIT 10-inch diameter pipe is not allowed. Please revise design to 12-inch. 6-inch Fire hydrants are not permitted for commercial developments. Please revise design to 8-inch fire hydrants.
TFD MWP Initial Review REVIEW COMPLETED Bluebeam is not available for stamping