Review Status: Requires Resubmit

Review Details: WATER MASTER PLAN - SINGLE PHASE v.1

Plan Number - TW-MWP-0324-00013
Review Name: WATER MASTER PLAN - SINGLE PHASE v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TW Administrative Completeness PENDING ASSIGNMENT
TW Hydraulic Modeling Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TFD MWP Initial Review REQUIRES RESUBMIT Update MWP to include required fire flow.
Based on the information provided, (5,415 sq. ft., Type VB construction) required fire flow is 2,000gpm for 2 hours. Provided by 2 hydrants within 400' of all portions of the building.