Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Plan Number: TW-MWP-0225-00005
Parcel: 120052770

Review Status: Requires Resubmit

Review Details: WATER MASTER PLAN - SINGLE PHASE v.1

Plan Number - TW-MWP-0225-00005
Review Name: WATER MASTER PLAN - SINGLE PHASE v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TW Administrative Completeness PENDING ASSIGNMENT
TW Hydraulic Modeling Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TFD MWP Initial Review Fast REQUIRES RESUBMIT Please revise your required fire flow, please note the requirement is 25% OF the value in table B105.1(2), or provide hydrants in accordance with IFC 2024 Appendix C for the fire flow listed. Please provide the location for the Underground fire line (there is a note on the drawing but piping is not shown).