Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Requires Resubmit
Review Details: WATER MASTER PLAN - OVERALL/PHASED v.1
Plan Number - TW-MWP-0223-00031
Review Name: WATER MASTER PLAN - OVERALL/PHASED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
TW Administrative Completeness | PENDING ASSIGNMENT | ||||
TW Hydraulic Modeling Review | PENDING ASSIGNMENT | ||||
TW Issue Invoice | PENDING ASSIGNMENT | ||||
TW Managerial Review | PENDING ASSIGNMENT | ||||
TW Verify Fees Paid | PENDING ASSIGNMENT | ||||
TFD MWP Initial Review | REQUIRES RESUBMIT | Buildings D-M shall have the type of construction provided and square footage to determine proper fire flow requirements Notes shall be made as to the buildings that will be sprinklered All sprinklered building shall have a fire hydrant within 600' of the furthest part of the building as the hose lays and not a "circle" Streets where hydrants are not needed for building protection but traffic protection shall have hydrants spaced not exceeding 1,000 ft. Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |