Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Plan Number: TW-MWP-0223-00031
Parcel: 13228765A

Review Status: Requires Resubmit

Review Details: WATER MASTER PLAN - OVERALL/PHASED v.1

Plan Number - TW-MWP-0223-00031
Review Name: WATER MASTER PLAN - OVERALL/PHASED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TW Administrative Completeness PENDING ASSIGNMENT
TW Hydraulic Modeling Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TFD MWP Initial Review REQUIRES RESUBMIT Buildings D-M shall have the type of construction provided and square footage to determine proper fire flow requirements
Notes shall be made as to the buildings that will be sprinklered
All sprinklered building shall have a fire hydrant within 600' of the furthest part of the building as the hose lays and not a "circle"
Streets where hydrants are not needed for building protection but traffic protection shall have hydrants spaced not exceeding 1,000 ft.
Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033