Permit Number: TS-PRM-1225-00499
Parcel: 10818716A

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-1225-00499
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2025 Commercial Electrical Standard APPROVED
12/10/2025 Outdoor Lighting Standard APPROVED
12/23/2025 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-1225-00499 1745 E. River Rd. #145. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) The site is in a scenic corridor. The allowed square footage calculation is 1.25 sq ft per linear foot of frontage. The frontage listed for this site is 30, 1.25 x 30= 37.5 sq ft. The proposed sign area is 44.6 sq ft, which is over the allowed square footage amount. Please reduce the square footage to the amount allowed by code.
2) Lag Shield bolts are typically for use in masonry or concrete material where they can expand, not wood and stucco. Please provide an adequate anchor to be used in a plywood/stucco wall. Consult an engineer for recommendation.
3) Please outline the tenant space on the site map.