Permit Number: TS-PRM-1125-00487
Parcel: 11004345J

Review Status: In Review

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-1125-00487
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Signs Standard PENDING ASSIGNMENT
11/21/2025 Commercial Electrical Fast REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-1125-00487 (3225 N SWAN RD Unit:UNIT 119 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7 and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

2. Provide the number of circuits required and the amp rating of each sign.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/21/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor lighting Review TS-PRM-1125-00487 (3225 N SWAN RD Unit:UNIT 119 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24 hour programmable timer installed to comply with the COT Outdoor Lighting Code"