Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2026 Signs Standard REQUIRES RESUBMIT 04/03/2026 Review Comments:
Sign Review TS-PRM-1125-00487 3225 N. Swan Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1. #10 screws will not be sufficient to support the weight of the sign against shear and tensile loads in the wall construction provided. Please provide the necessary fasteners, detail drawings or hire a structural engineer to specify the fastener type, the structural calculation and detail drawings that meets the requirements of the 2018 IBC 3107.1 Signs and Chapter 1603.1.4. The primary requirements for such signs will be related to structural stability as addressed in Chapter 16 and IBC Appendix H.
2. All dimensions must be in feet.decimal format, not feet and/or inches. Ex- 1’9” = 1.75’ . 162.5” = 13.63’.
3. Contractor of Record’s (SPG Companies) name and contact information must be listed on all pages of the drawings and location map.