Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.2
Permit Number - TS-PRM-1125-00487
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2026 | Commercial Electrical Fast | APPROVED | |||
| 01/02/2026 | Outdoor Lighting Standard | APPROVED | |||
| 01/16/2026 | Signs Standard | REQUIRES RESUBMIT | Sign Review TS-PRM-1125-00487 3225 N. Swan Rd. #119. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049. 1) TC-COM-1025-01906 will need to be paid for and issued prior to the sign being approved. It is currently in Needs Resubmittal status. 2) Please outline the tenant space on the site plan and indicate the frontage amount. 3) Provide the overall height from the top of curb to the top of the sign. 4) Window graphics do not require permits, but also cannot occupy more that 30% of the window surface. Please remove window graphics from application. 5) Provide the construction materials the wall is made of. Do not list only finishing materials like stucco. |