Permit Number: TS-PRM-1122-00050
Parcel: 12110005D

Address:
4770 E GRANT RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.2

Permit Number - TS-PRM-1122-00050
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2022 Signs REQUIRES RESUBMIT Add your own notes to your own plan - do not use staff's marked up plan set for submittal. See the red notes on staff's plans and add the volts, amps, circuits for the sign, and a note that says "signs will be shut off at midnight via timer" and add the note "dedicated circuit will be provided and labeled circuits will be provided at breaker panel" Your application is fine, do not resubmit that document, just resubmit the plan sheet and location map set. Thank you.