Permit Number: TS-PRM-1122-00019
Parcel: 13316021D

Address:
6616 E GRANT RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-1122-00019
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2022 Signs REQUIRES RESUBMIT RE: sign review
For: wall signs, change copy on freestanding sign, new menu boards
AT: Taco Bell / 6616 E Grant Road
Sign permit: TS-PRM-1122-00019
Reviewer: H. Thrall
Date: 12/5/22

Codes: Unified Development Code (UDC), 7A Sign Standards, National Electrical Code (NEC), Tucson- Pima County Outdoor Lighting Code (OLC), International Building Code (IBC) 2018
General:
1) Provide permit application.
2) Revise plans so that all dimensions are in decimal feet and list the total sign area of each sign
3) Revise plan set so each sign corresponds to the application document (i.e. sign A, B, C, etc.)
4) On the plan set, call out the approximate height on the elevation for each sign.

5. UDC:
a. acknowledge sign area proposed is within allowance, thank you.

6. NEC / OLC:
a. menu board - provide note that dedicated sign circuit shall be provided and labeled at the breaker panel
b. menu board – label location of shut off switch
c. menu board – add note that digital board shall dim to 200 Nits from sunset to business closure by photocell or laser sensor
d. order station canopy plans show “uplighting”, however, uplighting does not meet the outdoor lighting code. Clarify light sources shall be full cut off shield lights, and provide volts, amps, circuits, shut off, lighting type and color temp.
e. add notes throughout each page of the plan set that: a timer shall be provided to shut off each sign at the later of midnight or business closure, signs shall have dedicated circuit labeled at breaker panel, maximum color temperature is 4400k
f. show shut of switch for each sign – wall and canopy signs - label clearly on plan

7. IBC 2018:
a. menu board – list size / number of bolts used
b. for order station canopy – provide engineered plans
c. provide type /sizes / typical number of mounts for each sign, with type of wall for each mount – wall and canopy signs

enlarge sign descriptions and match the sheet for each construction / electrical data PER SIGN

Revise all plan sheets and resubmit.