Permit Number: TS-PRM-1025-00439
Parcel: 13316013E

Address:
6610 E GRANT RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.2

Permit Number - TS-PRM-1025-00439
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2025 Commercial Building Standard APPROVED
11/20/2025 Commercial Electrical Standard REQUIRES RESUBMIT See outdoor lighting review
11/20/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TS-PRM-1025-00439 (6610 E GRANT RD TUCSON, AZ 85715)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Please specify how the menu-boards are going to be illuminated. Are they internally illuminated, or are they digital menu-boards? Reference signs J & I.
2. If they are digital menu-boards, add the following Note to the referenced sheets: “As per the City of Tucson Outdoor Lighting Code the Electronic Message Center as shown on this page shall automatically dim to 200 NITS or less from sunset to sunrise. OLC 501.5.2”.
3. If internally illuminated, add the following notes: “As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/08/2025 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-1025-00439 6610 E. Grant Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) This site is allowed 3 sq ft per linear foot of building frontage. The building frontage is 62. 62 x 3 = 186 sq ft of allowed sign area. You are proposing almost twice the amount of allowed square footage. Please reduce the amount of signage to meet code allowances.
2) Contractors are required to have an active City of Tucson business license. Please obtain a business license from the Business License Department and add the number to the application.
3) Sealed Engineering will be required to utilize the existing sign base for the freestanding sign.
4) The setback needs to be noted for the leading edge of the sign to the face of the curb on Grant Rd. The site plan also needs to show the SVTs for the entryway off of Grant Rd per section 5.1 Sight Visibility Triangles of the Uniform Development Code.
5) Location of disconnect switch on the freestanding signs must be shown on plans.
6) Update the Amperage on all signs as not all of the signs will pull the same amount of amperage.