Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-1025-00436
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/12/2025 | Commercial Building Standard | APPROVED | |||
| 10/17/2025 | Commercial Electrical Fast | APPROVED | |||
| 10/17/2025 | Outdoor Lighting Standard | APPROVED | |||
| 10/30/2025 | Signs Standard | REQUIRES RESUBMIT | Sign Review TS-PRM-1025-00436 2920 S. Park Ave. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. 1) Welding in the field requires a special inspection certificate. Please provide a special inspetion form for the welding called out on the plans. 2) ⅜" x 1- 1/2” all thread fastener will be insufficient as an anchor to hold the sign to the wall. Please provide a secure method of attachment. Consult an engineer for recommendation. 3) Minimum setback requirement for freestanding signs is 20’ from leading edge of sign to face of curb. Revise to meet setback requirements. 4) Include sight visibility triangles on site plan per section 5.1 of the UDC. |