Permit Number: TS-PRM-1025-00427
Parcel: 105110620

Address:
4220 N ORACLE RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-1025-00427
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2025 Commercial Electrical Fast REQUIRES RESUBMIT Electrical cannot be approved until outdoor lighting has been approved.
10/13/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TS-PRM-1025-00427 (4220 N ORACLE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. The painted wall signs all depict new outdoor lighting fixtures being added to illuminate the wall painting. These lights require compliance with the outdoor lighting code.
2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
3. List the Lighting Area per OLC (Typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
6. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
7. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

8. Specify any exceptions used.

9. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/29/2025 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-1025-00427 4220 N. Oracle Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code.
1) Site frontage will be based on building frontage, not street frontage due to shared/connected parking areas with surrounding properties. Please provide building frontage for allowed square footage calculations.
2) Signs C, D- Provide materials the wall is constructed of. Specify the type of anchor being used to mount the signs to the wall, not non-corrosive fastener.
3) Signs E, F, G, H & I- sign area needs to include all decorative borders/embellishments per Sign Standards 7A.6.1