Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-1025-00418
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2025 | Commercial Electrical Fast | APPROVED | |||
| 10/09/2025 | Outdoor Lighting Standard | APPROVED | |||
| 10/27/2025 | Signs Standard | REQUIRES RESUBMIT | Sign Review TS-PRM-1025-00418 4016 N. 1st Av. #100. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. 1) #10 screws are not adequate in a masonry construction. If using anchors, please specify the size and type being used. 2) Add the following verbiage to the drawings: A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign. 3) Show location of electric disconnect switch on detail drawings. |