Permit Number: TS-PRM-1023-00582
Parcel: 14042035A

Address:
7101 S TUCSON BL

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-1023-00582
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2023 Commercial Building APPROVED
11/03/2023 Signs APPROVED RE: 3 freestanding signs (2 in center traffic island, 1 on north side of entry drive)
For: Tucson Airport Authority campus entry
AT: 7101 S Tucson Bl
Date: 11/3/23
Reviewer: H. Thrall (Heather.Thrall@tucsonaz.gov)

STATUS: Sign Divison approval, subject to the following notations / conditions

Codes: applicable codes for Tucson Airport Authority campus, per PDSD procedures, are only technical: National Electrical Code (NEC) 600, Tucson-Pima County Outdoor Lighting Code (OLC), International Building Code (IBC) 2018

1. Per Real Estate Division at Dept of Transportation and Mobility, the Tucson Bl right of way has been vacated and combined into the center island where two signs are placed.

2. For safety - "bullnose" or round the edges of the sign structures and the art structures.

3. Add a licensed sign contractor to this project and provide a sign permit application on their behalf, state law.

4. All sign lighting shall be internal only.
11/08/2023 Sign Post Review PENDING ASSIGNMENT
11/06/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Indicate on the lighting calculation plan whether or not a special inspection for Outdoor Lighting is required. OLC section 104.2.2, 106.2.

2. Provide information on the Electrical Site plan for the feeder conduit and conductor sizes and types from the existing TEP transformer and the new 150KVA Mini Power Zone. Provide for voltage drop due to the distance or adjustment factors for conductors if applicable. NEC art 310.

3. Provide a grounding detail for the Mini Power Zone. NEC 250.32.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.