Permit Number: TS-PRM-1023-00567
Parcel: 13409018D

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-1023-00567
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2023 Signs REQUIRES RESUBMIT Sign review; replacement canopy and wall signs and change copy on pole sign
For: Taco Bell / 8578 E Broadway Bl
Sign permit: TS-PRM-1023-00567
Date: 11/1/23
Reviewer: H. Thrall (Heather.Thrall@tucsonaz.gov)

Codes: Unified Development Code (UDC) 7A, Sign Standards, National Electrical Code (NEC) 600, Tucson-Pima County Outdoor Lighting Code (OLC), International Building Code (IBC) 2018

1. UDC:
A) Based on street development frontage of 154' along Broadway Blvd, acknowledged that sign area and sign types are within code allowances, thank you.

B) note the heights from grade to top of sign on each applicable elevation
C) provide sign dimensions in decimal feet
D) update the cabinet size for the pole sign at 6.75 x 10.25

2. NEC: /OLC: add the following notes to each sheet:
A) dedicated sign circuit shall be provided and labeled at breaker panel
B) all signs shall be UL or MET listed
C) all signs shall have UL sticker, manufacturer sticker and installer sticker on the side of the sign
D) safety lock out shall be provided in circumstances where disconnect switch is not immediately visible to the sign
E) Timer shall be provided and set to midnight, to be verified at inspection (if open past midnight, set to close time)
F) Maximum color temperature shall not exceed 4400k
G) canopy signs need to have the volts, amps, circuits and shut off information
H) 5000k color temp is listed in the diagram set, update to indicate max 4400k LED

3) IBC:
A) provide clarification what canopy letters are affixed to / on - i.e. alum posts?
B) provide a schedule of fasteners to be used depending on wall type

Resubmit on the portal with the updated notations on the plan set. Please email me if you have any questions. Thank you