Permit Number: TS-PRM-0926-00349
Parcel: 13342634L

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0926-00349
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2026 Commercial Building Standard APPROVED
10/16/2026 Commercial Electrical Standard APPROVED
10/21/2026 Sign Post Review Express PENDING ASSIGNMENT
10/16/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

PAGE 5: Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24-hour programmable timer installed to comply with the COT Outdoor Lighting Code.

The means of controlling the specific “off” curfew shall be by a 24-hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:

Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.

Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)

Please show exact location of retrofit LED
10/21/2026 Signs Standard REQUIRES RESUBMIT 10/21/2026 Sign Review TS-PRM-0926-00349. Plan review for the above referenced structure has been completed by Ginger Neely. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Pdsd_signpermits@tucsonaz.gov or 520-837-5017 (voice mail only).

Please resubmit the updated sign package in addition to a comment response letter addressing the following:

1. Please provide measurements in decimals instead of feet - inches (IE 2.5’ vs 2’-6”)
2. On the site plan, provide dimensions of property for 6750 E Tanque Verde Rd
a. The “driveway” as outlined on the plan does not seem to be part of the parcel 13342634L for Public Storage. Please provide correct parcel boundary.
b. Please provide verification of owner permission for use of the property for parcel 13342634M for the monument sign E01
3. Interior signs do not need a permit, ok to remove from plan set. Be sure to update any page indexes and page numbers as needed.
4. Banners require a temporary sign compliance certificate, which is a separate permit. Please provide the temporary sign compliance certificate(s) for the banner signs.
5. No more than thirty percent of total window surface may be covered. Door sign designated E09 exceeds this. Please update.
6. Please add contractor information to the permit in TDC Online. The contractor must have a valid Arizona ROC license number valid for the scope of work and a business license.
09/29/2026 Signs Application Completeness Express REVIEW COMPLETED