Permit Number: TS-PRM-0925-00388
Parcel: 141185450

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.2

Permit Number - TS-PRM-0925-00388
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-0925-00388 (9537 E OLD VAIL RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7 and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

2. Provide the number of circuits required and the amp rating of each sign.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/07/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TS-PRM-0925-00388 (9537 E OLD VAIL RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. Add the following notes to each Illuminated Sigh sheet:
“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

2. Provide permanent curfew “off” time sign or notice:
Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.
Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/23/2025 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-0925-00388 9537 E. Old Vail Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code.
Application:
1) Note frontage amount in box on application. Frontage is calculated either by street frontage, if the site will have isolated parking with no access to any other parcels and no shared parking with any other businesses or if shared parking or access to other properties exists, then the applicant may use the length of the building facing the roadway. This is used in calculating allowed area and must be provided by the applicant.
2) Your business license has not been paid for and is not yet active. Please pay for your business license as the permit will not be issued until this is complete.

Sign Drawings:
1) All measurments need to be in feet.decimal, not feet and/or inches.
2) Provide materials the wall is constructed of, not just finishing material like EIFS or stucco on cross section drawing.
3) Specify type of studs being used to mount sign to wall.
4) Show location of disconnect switch on cross section detail.
5) Address numerals do not need sign permit. Please remove from sign package.

Location Map:
1) Location map needs to show building layout and include North arrow.
2) Sign designations of A, B, C need to be noted on location map.
3) Show frontage length on location map.